Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop E
Sequence Number 6
Notes
Date Text
2009-02-06 17:40:15** DENIED REVIEW **
  
 ** 6TH REVIEW FAILED. THIS IS THE THIRD REVIEW UNDER
 ACTUAL PERMIT APPLICATION.
  
 1) NOTE: PLEASE SEE ALL PREVIOUS REVIEWS WITH RESPECT
 TO MINIMUM CODE COMPLIANCE REQUIRED FOR CHAPTER 13.
 PLEASE SEE THAT COMPLIANCE FOR FLORIDA BUILDING CODE
 CHAPTER 13 HAS NOT BEEN ACHIEVED.
 THE SUBMITTED METHOD *A* CALCULATIONS ARE FOR *WHOLE
 BUILDING COMPLIANCE*. WHEN SUBMITTING ENERGY
 CALCULATIONS FOR WHOLE BUILDING COMPLIANCE THAT IS JUST
 WHAT THE CODE REQUIRES. PLEASE SEE SECTION13-400.0.A,
 13-400.2.A.2 WHICH IS JUST TWO SECTIONS WHICH STATES
 ONCE ALL BUILDING COMPONENTS ARE KNOWN THEN AND ONLY
 THEN IS METHOD *A* PERMITTED TO BE USED.
 ON PREVIOUS REVIEWS THIS REVIEW GAVE ITEMS ON PLANS
 WHICH WERE NOT IN THE ENERGY CALCULATIONS AND ITEMS ON
 THE PLANS WHICH WERE NOT IN THE INPUT DATA REPORT OF
 THE SUBMITTED CALCULATIONS.
 IT IS CLEAR ON THE PLANS THAT THE INFORMATION ON PLANS
 DOES NOT COORDINATE WITH PLANS. SOME EXAMPLES WILL BE
 GIVEN ONCE AGAIN AS A BENEFIT TO DESIGN TEAM IN AN
 EFFORT TO MEET ABSOLUTE *MINIMUM CODE COMPLIANCE*.
  
 FOR EXAMPLE: INTERIOR LIGHTING ON THE IDR STATES A
 TOTAL OF 45-32WATT FIXTURES AND A TOTAL OF 30-32WATT
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE FIXTURES ON THE
 FIXTURE LEGEND ARE NOT EVEN 32WATT FIXTURES. IN FACT
 ONE FIXTURE WHICH IS FIXTURE *A* STATES THERE ARE 4-40W
 BULBS AND THE OTHER STATES 2-40W BULBS.
 THE *A* FIXTURE WHICH STATES 4-40W BULBS CAN NOT
 POSSIBLY BE 32WATTS BASED ON THE INFORMATION STATED ON
 THE INPUT DATA REPORT OF THE SUBMITTED SIGNED AND
 SEALED ENERGY CALCULATIONS.
  
 FOR EXAMPLE: THE EXTERIOR LIGHTS ON THE IDR ONLY STATES
 2-150W FIXTURES. THIS IS NOT POSSIBLE. THIS METHOD OF
 CALCULATION SUBMITTED IS METHOD *A* FOR WHOLE BUILDING
 COMPLIANCE AND THE LIGHTING SHOWN ON THE ELECTRICAL
 PLANS IS FAR GREATER THAN THAT SHOWN ON THE IDR. IN
 FACT THE FIXTURES ON THE PLANS ARE 100W, 320W AND 400W
 FIXTURES. HOW IS IT POSSIBLE THAT THE IDR ONLY SHOWS
 TWO 150W FIXTURES?
  
 THE COMMENT FROM PREVIOUS REVIEW AS WELL AS THIS REVIEW
 IS ALSO FOR ALL INFORMATION ON PLANS TO COORDINATE WITH
 THE INPUT DATA REPORT. THIS COMMENT IS FOR ALL TRADES
 AND FOR ALL REVIEWS WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
 PLEASE SEE FBC 13-101.1, 13-400.3.A, 13-400.3.B,
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3. THESE ARE
 ONLY A FEW SECTIONS NOTED FOR ELECTRICAL LIGHTING.
 PLEASE ALSO SEE 13-400 THROUGH 13-414 FOR COMPLIANCE OF
 ALL OTHER BUILDING COMPONENTS SUCH AS INSULATIONS,
 DOORS, WINDOWS, FLOOR, PIPING, WATER HEATING ETC. THESE
 ARE ONLY A FEW ITEMS NOTED.
 PLEASE SEE CHAPTER 13.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 REQUIRED TRANSFER SWITCH REQUIRED TO MEET HB 7121,
 701.7, 110.3. THE PROPOSED *BOLT-ON* LOCKS NOT ONLY
 WOULD VOID LISTING OF EQUIPMENT IT ALSO DOES NOT MEET
 THE SECTIONS OF THE CODE GIVEN.
 ANY EQUIPMENT USED TO TRANSFER POWER SHALL BE LISTED
 FOR ITS USE.
 THE ITEM BEING SUBMITTED FOR USE IS NOT PERMITTED.
 ANYONE WHO HAS TWO KEYS COULD OPERATE BOTH BREAKERS AT
 THE SAME TIME WHICH WOULD PERMIT POWER FROM BOTH SIDES
 BEING ON AT THE SAME TIME. THIS IS NOT ONLY A FIRE
 HAZARD BUT AS WELL AS A LIFE SAFETY HAZARD.
  
  
 3) NOTE: PLANS HAVE BEEN SUBMITTED FOR SIX REVIEWS. ON
 THE LAST/PREVIOUS REVIEW A NOTICE WAS GIVEN WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE PER FS
 553.80(2)(B).
 WHEN SPECIFIC CODE SECTIONS ARE REPEATED THREE OR MORE
 TIMES FOR THE SAME CODE SECTION VIOLATION THE STATE
 STATUTE REQUIRES A FEE ASSESSED. THIS FEE AS NOTED PER
 STATUTE SECTION GIVEN IS BASED ON THE AMOUNT OF THE
 BASE PERMIT FEE ATTRIBUTED TO PLAN REVIEW TIMES FOUR.
 IN THE CITY OF WEST PALM BEACH THE PORTION OF THE BASE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW IS 30% (PERCENT)
 OF THE BASE PERMIT FEE. THE BASE PERMIT FEE ON THIS
 PROJECT IS $4,500.00. THIS IS NOT THE OTHER FEES FOR
 FIRE REVIEW ETC.
 THE 30% OF THE $4,500.00 IS $1,350.00. THIS IS THE
 AMOUNT TIMES FOUR.
 $1,350.00 TIMES FOUR IS $5,400.00. THIS IS THE AMOUNT
 REQUIRED BY FLORIDA STATUTES TO BE ASSESSED. THIS IS
 NOT A LOCAL FEE OR LOCALLY REQUIRED. THIS IS A REQUIRED
 FEE BY THE STATE.
 IT IS IMPORTANT TO KNOW THAT THE FEE IS FOR EACH TIME
 AFTER THEREFORE IT IS IMPERATIVE FOR CORRECTIONS TO BE
 MADE AND FOR PLANS AND SUBMITTED ENERGY CALCULATIONS TO
 MATCH AND TO MEET MINIMUM CODE. ONE SET OF ELECTRICAL
 PLANS, AND CALCULATIONS ARE BEING RETAINED BY THIS
 OFFICE FOR FILE. IT IS NOT THE INTENT OF THIS OFFICE TO
 SEND PLANS TO THE FLORIDA BOARD OF ENGINEERS FOR REVIEW
 AT THIS TIME HOWEVER THIS OFFICE MAY NOT BE LEFT WITH
 ANY CHOICE BASED ON THE NEXT REVIEW. PLEASE MAKE
 CORRECTIONS AS NOTED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  