Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop M
Sequence Number 5
Notes
Date Text
2008-12-20 11:44:21REVIEW #: 2ND (FOR PERMIT)
 ACTION: PASS W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 *******PROVISO*******
 PLEASE ADDRESS THE FOLLOWING PROIR TO INSTALLATION AND
 INSPECTION OF OUTDOOR MECHANICAL APPLIANCES:
 1. CONDENSER STANDS ARE DEFINED AS STRUCTURAL
 COMPONENTS PER FAC RULE 9B-72. PRODUCT APPROVAL IS
 REQUIRED. PROVIDE PRODUCT APPROVAL WITH APPROVING
 AGENCY COVER AND CORRESPONDING INSTALLATION
 INSTRUCTIONS.
 2. CONDENSERS ARE < 10' FROM THE ROOF EDGE. GUARDS ARE
 REQUIRED AT THIS LOCATION IN ACCORDANCE WITH FBCM
 304.10.
 3. PROVIDE SUBMITTAL DATA FROM OUTDOOR APPLIANCE
 MANUFACTURERS SHOWING THESE APPLIANCES ARE DESIGNED TO
 RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  