| Plan Review Notes For Permit 06040955 |
| Permit Number |
06040955 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-12-20 11:44:21 | REVIEW #: 2ND (FOR PERMIT) | | | ACTION: PASS W/ PROVISO | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | *******PROVISO******* | | | PLEASE ADDRESS THE FOLLOWING PROIR TO INSTALLATION AND | | | INSPECTION OF OUTDOOR MECHANICAL APPLIANCES: | | | 1. CONDENSER STANDS ARE DEFINED AS STRUCTURAL | | | COMPONENTS PER FAC RULE 9B-72. PRODUCT APPROVAL IS | | | REQUIRED. PROVIDE PRODUCT APPROVAL WITH APPROVING | | | AGENCY COVER AND CORRESPONDING INSTALLATION | | | INSTRUCTIONS. | | | 2. CONDENSERS ARE < 10' FROM THE ROOF EDGE. GUARDS ARE | | | REQUIRED AT THIS LOCATION IN ACCORDANCE WITH FBCM | | | 304.10. | | | 3. PROVIDE SUBMITTAL DATA FROM OUTDOOR APPLIANCE | | | MANUFACTURERS SHOWING THESE APPLIANCES ARE DESIGNED TO | | | RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|