Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop E
Sequence Number 5
Notes
Date Text
2008-12-23 13:58:21** DENIED 5TH REVIEW**
  
 2ND REVIEW UNDER PERMIT APPLICATION.
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS THE 5TH
 REVIEW FOR SOME ITEMS NOT BEING CODE COMPLIANT AND THE
 2ND REVIEW UNDER PERMIT APPLICATION AND STILL NOT
 HAVING CODE COMPLIANCE FOR SOME ITEMS. PLEASE SEE
 COMMENTS BELOW. PLEASE BE AWARE OF STATUTE AS THIS MAY
 BECOME AN ISSUE ON THE NEXT REVIEW IF COMMENTS ARE NOT
 ADDRESSED.
  
 2) NOTE: PLEASE SEE THAT COMPLIANCE FOR FLORIDA
 BUILDING CODE CHAPTER 13 HAS NOT BEEN ACHIEVED. ON THE
 PREVIOUS REVIEW THE COMMENT WAS MADE THAT THE VERSION
 SUBMITTED WAS NO LONGER IN EFFECT AS THE CODE HAD
 CHANGED. THE COMMENT WAS ALSO FOR ALL INFORMATION ON
 PLANS TO COORDINATE WITH THE INPUT DATA REPORT. THIS
 COMMENT IS FOR ALL TRADES AND FOR ALL REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
 PLEASE SEE FBC 13-101.1, 13-400.3.A, 13-400.3.B,
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3. THESE ARE
 ONLY A FEW SECTIONS NOTED FOR ELECTRICAL LIGHTING.
 PLEASE ALSO SEE 13-400 THROUGH 13-414 FOR COMPLIANCE OF
 ALL OTHER BUILDING COMPONENTS SUCH AS INSULATIONS,
 DOORS, WINDOWS, FLOOR, PIPING, WATER HEATING ETC. THESE
 ARE ONLY A FEW ITEMS NOTED.
 PLEASE SEE CHAPTER 13.
 THE RESPONSE NOTES FOR ELECTRICAL DO NOT CONTAIN ANY
 RESPONSE FOR THE PREVIOUS NOTE WITH RESPECT TO ENERGY
 CALCULATIONS.
  
 3) NOTE: PREVIOUS NOTES WERE MADE WITH RESPECT TO HOUSE
 BILL 7121 AND THE REQUIRED BACK UP POWER. THE RISER HAS
 NOW BEEN REVISED HOWEVER NO TRANSFER SWITCH DEVICE
 LISTED PER UL 1081 IS SHOWN. IN FACT THERE SEEMS TO BE
 SOME SORT OF INTER-LOCK WHICH MAY OR MAY NOT MEET
 701.7, 702.6, 110.3 ETC.
 PLEASE KNOW THE DEVICE MUST BE LISTED AND MEET THE FAIL
 SAFE OPERATION TO PREVENT SERIOUS INJURY OR DEATH.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS.
  
  
 4) NOTE: THE PLANS ARE STILL LISTING THE INCORRECT
 CODES IN DIFFERENT LOCATIONS. PLANS STILL SHOW THE 2002
 NFPA-70 FOR EXAMPLE. PLEASE SEE D-1, A-1A ETC.
 THE CODES SHALL BE LISTED AS FOLLOWS.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 ** THIS IS A MINIMUM FOR THIS TRADE ALONE. THIS DOES
 NOT INCLUDE OTHER CODES REQUIRED AS PART OF DESIGN
 INCLUDING NFPA-30A.
 FS 553.73, FBC 2004.
 ** PLANS WERE NEVER SUBMITTED FOR PERMIT APPLICATION
 UNTIL 10/2008 THEREFORE CODES WHICH WERE IN EFFECT IN
 2006 ARE NO LONGER VALID. THIS WAS NOTED IN ALL
 PREVIOUS REVIEW YET THIS IS STILL NOT ADDRESSED.
  
 5) NOTE: LIGHTING CONTROLS MUST COMPLY WITH FBC
 13-415.1.ABC.1.4. PLEASE BE SURE TO NOTE TIME CLOCK AS
 ASTRONOMICAL WITH A MINIMUM OF 10HR BATTERY BACK UP FOR
 PROGRAMMING.
  
 6) NOTE: PLEASE SEE 250..110,250.122 ETC FOR MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM WHAT IS BEING CALLED
 A PRE-WIRED GENERATOR TAP BOX.
 AS SHOWN THERE IS NOT EQUIPMENT GROUNDING CONDUCTOR FOR
 ANY METALLIC BONDING.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  