| Date |
Text |
| 2008-12-23 13:58:21 | ** DENIED 5TH REVIEW** |
| | |
| | 2ND REVIEW UNDER PERMIT APPLICATION. |
| | |
| | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS THE 5TH |
| | REVIEW FOR SOME ITEMS NOT BEING CODE COMPLIANT AND THE |
| | 2ND REVIEW UNDER PERMIT APPLICATION AND STILL NOT |
| | HAVING CODE COMPLIANCE FOR SOME ITEMS. PLEASE SEE |
| | COMMENTS BELOW. PLEASE BE AWARE OF STATUTE AS THIS MAY |
| | BECOME AN ISSUE ON THE NEXT REVIEW IF COMMENTS ARE NOT |
| | ADDRESSED. |
| | |
| | 2) NOTE: PLEASE SEE THAT COMPLIANCE FOR FLORIDA |
| | BUILDING CODE CHAPTER 13 HAS NOT BEEN ACHIEVED. ON THE |
| | PREVIOUS REVIEW THE COMMENT WAS MADE THAT THE VERSION |
| | SUBMITTED WAS NO LONGER IN EFFECT AS THE CODE HAD |
| | CHANGED. THE COMMENT WAS ALSO FOR ALL INFORMATION ON |
| | PLANS TO COORDINATE WITH THE INPUT DATA REPORT. THIS |
| | COMMENT IS FOR ALL TRADES AND FOR ALL REVIEWS WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | PLEASE SEE FBC 13-101.1, 13-400.3.A, 13-400.3.B, |
| | 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3. THESE ARE |
| | ONLY A FEW SECTIONS NOTED FOR ELECTRICAL LIGHTING. |
| | PLEASE ALSO SEE 13-400 THROUGH 13-414 FOR COMPLIANCE OF |
| | ALL OTHER BUILDING COMPONENTS SUCH AS INSULATIONS, |
| | DOORS, WINDOWS, FLOOR, PIPING, WATER HEATING ETC. THESE |
| | ARE ONLY A FEW ITEMS NOTED. |
| | PLEASE SEE CHAPTER 13. |
| | THE RESPONSE NOTES FOR ELECTRICAL DO NOT CONTAIN ANY |
| | RESPONSE FOR THE PREVIOUS NOTE WITH RESPECT TO ENERGY |
| | CALCULATIONS. |
| | |
| | 3) NOTE: PREVIOUS NOTES WERE MADE WITH RESPECT TO HOUSE |
| | BILL 7121 AND THE REQUIRED BACK UP POWER. THE RISER HAS |
| | NOW BEEN REVISED HOWEVER NO TRANSFER SWITCH DEVICE |
| | LISTED PER UL 1081 IS SHOWN. IN FACT THERE SEEMS TO BE |
| | SOME SORT OF INTER-LOCK WHICH MAY OR MAY NOT MEET |
| | 701.7, 702.6, 110.3 ETC. |
| | PLEASE KNOW THE DEVICE MUST BE LISTED AND MEET THE FAIL |
| | SAFE OPERATION TO PREVENT SERIOUS INJURY OR DEATH. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS. |
| | |
| | |
| | 4) NOTE: THE PLANS ARE STILL LISTING THE INCORRECT |
| | CODES IN DIFFERENT LOCATIONS. PLANS STILL SHOW THE 2002 |
| | NFPA-70 FOR EXAMPLE. PLEASE SEE D-1, A-1A ETC. |
| | THE CODES SHALL BE LISTED AS FOLLOWS. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | ** THIS IS A MINIMUM FOR THIS TRADE ALONE. THIS DOES |
| | NOT INCLUDE OTHER CODES REQUIRED AS PART OF DESIGN |
| | INCLUDING NFPA-30A. |
| | FS 553.73, FBC 2004. |
| | ** PLANS WERE NEVER SUBMITTED FOR PERMIT APPLICATION |
| | UNTIL 10/2008 THEREFORE CODES WHICH WERE IN EFFECT IN |
| | 2006 ARE NO LONGER VALID. THIS WAS NOTED IN ALL |
| | PREVIOUS REVIEW YET THIS IS STILL NOT ADDRESSED. |
| | |
| | 5) NOTE: LIGHTING CONTROLS MUST COMPLY WITH FBC |
| | 13-415.1.ABC.1.4. PLEASE BE SURE TO NOTE TIME CLOCK AS |
| | ASTRONOMICAL WITH A MINIMUM OF 10HR BATTERY BACK UP FOR |
| | PROGRAMMING. |
| | |
| | 6) NOTE: PLEASE SEE 250..110,250.122 ETC FOR MISSING |
| | EQUIPMENT GROUNDING CONDUCTOR FROM WHAT IS BEING CALLED |
| | A PRE-WIRED GENERATOR TAP BOX. |
| | AS SHOWN THERE IS NOT EQUIPMENT GROUNDING CONDUCTOR FOR |
| | ANY METALLIC BONDING. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |