Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop B
Sequence Number 5
Notes
Date Text
2009-01-07 12:33:18REVIEW IN ERROR
2009-01-07 12:18:21REFER TO DATA IN ENG ROW
2009-01-07 11:39:47NO COMMENTS
  
  
  
  
  
2008-12-19 15:09:39****CORRECTIONS****
 ****SECOND PERMIT PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004EXISTING BUILDING CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LISTS, NOT ADDRESSED
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.) IMPACT FEES MAY BE OWED TO PALM
 BEACH COUNTY. THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025.
  
 THE PLANS WERE STAMPED BUT THE RECEIPT WAS NOT
 PROVIDED. PLEASE PROVIDE.
  
 3.-4.) ADDRESSED.
  
 5.) DECLARE AN OCCUPANT LOAD, FBC10.
  
 HOW HAVE YOU ARRIVED AT AN OCCUPANT LOAD OF 16, 1000/8
 X 1980? SEE FBC1004.1, MUST USE EITHER DESIGN LOAD OR
 BASED ON FBC TABLE 1004.1.2, WHICHEVER IS GREATER. M
 AND B HAVE DIFFERENT OCCUPANT LOADS. SEE FBC309; IT
 APPEARS THAT HIS IS M OCCUPANCY, NOT B. PROVIDE MORE
 INFORMATION IN REGARDS TO THE USE OF THIS BUILDING TO
 JUSTIFY THE B OCCUPANCY CLASSIFICATION.
  
 4TH REVIEW, OCCUPANT LOAD SHOULD BE SF AREA / 30 PER
 FBC TABLE 1004.1.2. PLEASE REVISE OR EXPLAIN OCCUPANT
 LOAD.
  
 5TH REVIEW, OCCUPANT LOAD IS NOW CALCULATED AT 300SF
 PER OCCUPANT FOR MERCANTILE AREA. SEE PREVIOUS REVIEW
 AND FBC TABLE 1004.1.2, OCCUPANT LOAD CANNOT BE LESS
 THAN THE TABLE, 30 SF PER PERSON. A1-B SHOWS 1512 SF
 STOCKROOM AREA, WHERE IS THE STOCKROOM? THE BUILDING IS
 ONLY 1980SF, YET YOU ARE STATING THAT 1512 IS A STORAGE
 AREA, ONLY 468 MERCANTILE. OCCUPANT LOAD MUST BE
 DETERMINED. SEE OTHER COMMENTS.
  
 6.) ADDRESSED.
  
 7.) SEE PREVIOUS LIST. A/C STAND PRODUCT APPROVAL
 REQUIRED FAC9B72.
  
 8.) PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 10-16.) ADDRESSED.
  
 17.) PROVIDE ENERGY CALCS AND SIGN IN
 ALL APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 INCLUDE THE STRUCTURAL ENGINEER TO CERTIFY ENERGY
 COMPLIANCE, FBC13-103.1.1.1 AS HE IS REPONSIBLE FOR THE
 BUILDING SHELL.
  
 5TH REVIEW, ENERGY CALCS WERE NOT INCLUDED IN THE
 RESUBMITTAL. NO RESPONSE PROVIDED FOR THIS ITEM ON THE
 RESPONSE LETTER.
  
 18-26.) ADDRESSED.
  
 27.) IT APPEARS THAT THE ENGINEER HAS NOT DELCARED THE
 CORRECT OCCUPANT LOAD AND TWO EXITS ARE REQUIRED. THE
 TWO EXITS ARE TO BE REMOTELY LOCATED, FBC1014.2.1. THIS
 REQUIREMENT CANNOT BE DETERMINED DUE TO THE ENGINEER'S
 FAILURE TO ADDRESS THE COMMENT REGARDING OCCUPANT LOAD
 AND OCCUPANCY CLASSIFICATION.
  
 5TH REVIEW, ALL DOORS TO THE OUTSIDE ARE SHOWN AS
 EXITS. THE "EXIT" AT THE VESTIBULE IS OBSTRUCTED BY THE
 STORAGE ROOM DOOR, SEE FBC 1005.2. SHOW THE TWO
 REQUIRED EXITS AND COMPLIANCE WITH THE REQUIREMENT TO
 BE REMOTELY LOCATED. DOORS MARKED AS EXIT DOORS MUST
 COMPLY WITH THE REQUIREMENTS OF FBC CHAPTER 10.
  
 28.) ADDRESSED.
  
 29.) THE PLANS DO NOT SHOW THE ISO BOARD REQUIRED FOR
 THE WALLS (ENERGY CALCS). PLEASE CORRELATE. NOTE
 EXISTING CONDITIONS FOR EXISTING WALLS. ALL INFORMATION
 IS TO BE ON THE PLAN IF A TYPED NAME IS USED IN LIEU OF
 A SIGNATURE, SEE FBC13-103.1.1.1.
  
 5TH REVIEW, ENERGY CALCS HAVE BEEN REMOVED. BUILDING
 COMPONENTS CANNOT BE CONFIRMED.
  
 30.) ADDRESSED.
  
 CONTRACTOR WAS CALLED IN AN ATTEMPT TO RESOLVE SOME OF
 THE OUTSTANDING ISSUES.
  
  