| 2008-10-28 11:51:26 | |
| | ** DENIED 4TH REVIEW** |
| | |
| | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. |
| | SCOPE OF WORK NOT COMPLETE. PLANS AND PERMIT PACKAGE |
| | NOT COMPLETE FOR MINIMUM CODE COMPLIANT REQUIRED. |
| | ** THE SAME PLANS ARE BEING RESUBMITTED WITHOUT ANY |
| | CORRECTIONS. THE LAST REVISED PLAN DATE IS FROM SEPT OF |
| | 2006. |
| | |
| | |
| | 1) NOTE: PLEASE CLEARLY LABEL AND IDENTIFY ALL |
| | CLASS/DIVISION LOCATIONS PER NEC 514, NFPA-30. |
| | PLEASE PROVIDE LAYOUT FOR DISTANCES OF DISCONNECTING |
| | MEANS FOR PUMPS ETC. |
| | THIS WAS NOTED ON PREVIOUS REVIEWS. |
| | |
| | 2) NOTE: PLANS REFLECT THE 2002 NFPA-70 WHICH IS NO |
| | LONGER ADOPTED. PLEASE SEE THE 2004 FBC WITH THE |
| | 2006/2007 REVISIONS WHICH ADOPTED THE 2005 NFPA-70 |
| | |
| | 3) NOTE: PLEASE SEE SEALS NEED TO BE CLEAR AND VISIBLE |
| | WITH ALL INFORMATION ON SAID SEALS. |
| | FAC 61G15-23.002, FS 471.025 |
| | THE NEW SEALS ON PLANS ARE VERY FAINT. |
| | |
| | 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE NO LONGER VALID BASED ON THE LATEST ADOPTED |
| | VERSION. AS THE PERMIT APPLICATION WAS NOT MADE UNTIL |
| | RECENTLY THE DATE OF APPLICATION STATES THE CODE AND |
| | DESIGN. |
| | PLEASE SEE 13-400.3.A, .3.B, .3.C AS THE ADOPTED |
| | VERSIONS SHALL BE 2.5. |
| | PLEASE BE SURE ALL COMPONENTS ON PLANS ARE ACCURATE IN |
| | THE INPUT DATA REPORT. |
| | THE LIGHTING ETC DOES NOT CORRELATE. |
| | PLEASE SEE THE SUBMITTED VERSION IS METHOD *A*. PLEASE |
| | SEE 13-101.1.3 FOR REQUIRED METHOD FOR RENOVATED |
| | BUILDINGS.. |
| | PLEASE BE SURE TO SEE 13-415.2.ABC.1.1,.1.2 AND .1.3 |
| | FOR LIGHTING PERFORMANCE. |
| | |
| | 5) NOTE: THIS IS THE FORTH TIME THE RISER IS STILL |
| | SHOWING *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE |
| | FIRST MEANS IF DISCONNECT WHICH IS NOT PERMITTED. |
| | 250.6,250.24 ETC |
| | |
| | 6) NOTE: PLEASE SHOW A DETAIL FOR THE DISCONNECTING |
| | MEANS. A MUSHROOM BUTTON IS SHOWN, HOWEVER NO |
| | INFORMATION/DETAIL IS SHOWN ON HOW THIS WILL BE TIED |
| | INTO THE BRANCH CIRCUITS REQUIRED TO BE SHUT DOWN. |
| | 514.11 |
| | PLEASE SEE 514 IN HAND BOOK AS EXAMPLES ARE SHOWN. |
| | |
| | 7) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS |
| | HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY |
| | 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES |
| | ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL |
| | REMODEL, ETC INSTALL PROVISIONS FOR A COMPLETE |
| | EMERGENCY BACK UP GENERATOR SYSTEM. THIS WILL |
| | SUBSTANTIALLY CHANGE THE PLANS SUBMITTED. |
| | PLEASE SEE 701 AND 2002 NFPA-110 |
| | PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER |
| | NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME |
| | MOVER ETC ETC. |
| | PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 |
| | ETC |
| | |
| | 8) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| | DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. IN FACT THE PERMIT APPLICATION HAD AN APPLIED |
| | VALUE OF $400K AND WAS REDUCED TO $200K. |
| | |
| | |
| | |
| | ** AS THERE ARE SEVERAL ITEMS NOT YET SHOWN A COMPLETE |
| | REVIEW COULD NOT YET BE DONE. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |