| Date |
Text |
| 2007-02-26 10:17:20 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | WPB MUNICIPAL CODES |
| | |
| | PLAN REVIEW ONLY |
| | |
| | ...FROM PREVIOUS REVIEWS: |
| | |
| | 1. DELETED |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | A. OK |
| | B. OK |
| | 7. OK |
| | A. OK |
| | B. OK |
| | 8. OK |
| | |
| | 9. SHT P-1 SANITARY RISER DIAGRAM AND |
| | FLOOR PLAN, FLOOR DRAINS ARE NOT |
| | APPROVED INDIRECT WASTE RECEPTORS. A |
| | FLOOR SINK OR HUB IS REQUIRED FOR |
| | INDIRECT WASTE. FLOOR SINKS SHALL BE |
| | LOCATED AS TO NOT BE A TRIPPING HAZARD |
| | AND SHALL BE LOCATED UNDER THE COUNTER |
| | SPACE OR EQUIPMENT. SECTION SECTIONS |
| | 802.3 AND 802.3.2. |
| | ****RESPONSE NOTED, BUT THE CONDENSATE FROM THE COOLER |
| | IS STILL INDICATED AS DRAINING INTO A FLOOR SINK, AND |
| | SAFE WASTES ARE NOT APPROVED. EACH FLOOR SINK SHALL BE |
| | INDIVIDUALLY CONNECTED TO THE VENTED LINE AND HAVE ITS |
| | OWN TRAP. SECTIONS 901.2.1 AND 1002.1. |
| | ******RESPONSE NOTED, BUT INDICATE THE TYPE OF FIXTURE |
| | DRAINING INTO THE '2" IW W/AIR GAP'. THE DRAIN |
| | CONNECTING TO THE MOP SINK DRAIN AS SHOWN IS A SAFE |
| | WASTE AND IS NOT APPROVED. ALL INDICREC WASTE RECEPTORS |
| | SHALL BE SEPARATELY TRAPPED AND CONNECT TO THE VENTED |
| | STACK SEPARATELY AS INDICATED IN THE PREVIOUS REVIEW. |
| | NO DRAIN IS INDICATED FOR THE ICE MAKER. PLEASE |
| | INDICATE WHERE THIS WILL BE DRAINING TO. AN INDIRECT |
| | WASTE RECEPTOR WILL BE REQUIRED FOR THE ICE MAKER. |
| | SECTION 802. |
| | |
| | 10. SHT P-1 WATER HEATER DETAIL: AIR |
| | CHAMBERS OK |
| | - THERMAL EXPANSION CONTROL IS |
| | REQUIRED AT THE WATER HEATER. PLEASE |
| | INDICATE METHOD. SECTION 607.3.2. |
| | ****NOT ADDRESSED |
| | ******RESPONSE NOTED, BUT THE P/T DISCHARGE VALVE IS |
| | NOT APPROVED FOR THERMAL EXPANSION CONTROL. PLEASE SEE |
| | SECTION 504.4. |
| | |
| | 11. OK |
| | 12. OK |
| | |
| | 13. GREASE INTECEPTOR SHALL BE INSPECTED |
| | AND SIZED BY LYNN MASSON ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT HER AT (TEL) |
| | (561) 822- 2271, (FAX) (561) 822-2279, |
| | OR E-MAIL [email protected]. MUNICIPAL |
| | CODE SECTION 3434. |
| | ****WAITING FOR A RESPONSE FROM LYNN. I WILL CONTACT |
| | HER. |
| | ******A NEW 750 GAL. INTERCEPTOR IS REQUIRED PER |
| | ENVIRONMENTAL COMPLIANCE. SEE ATTACHED SHEET. PLEASE |
| | INDICATE ON PLANS. A SEPARATE PERMIT IS REQUIRED FOR |
| | THE GREASE INTERCEPTOR. |
| | |
| | 14. OK |
| | |
| | **************NEW COMMENT************** |
| | |
| | 1B. OK (PLEASE REMOVE ALL VOIDED SHEETS FROM THE ONE |
| | SET OF PLANS). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SUBMIT ONE SET OF REPLACED SHEETS FOR COMPARISON |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |