Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop P
Sequence Number 3
Notes
Date Text
2007-02-26 10:17:20DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODES
  
 PLAN REVIEW ONLY
  
 ...FROM PREVIOUS REVIEWS:
  
 1. DELETED
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 A. OK
 B. OK
 7. OK
 A. OK
 B. OK
 8. OK
  
 9. SHT P-1 SANITARY RISER DIAGRAM AND
 FLOOR PLAN, FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB IS REQUIRED FOR
 INDIRECT WASTE. FLOOR SINKS SHALL BE
 LOCATED AS TO NOT BE A TRIPPING HAZARD
 AND SHALL BE LOCATED UNDER THE COUNTER
 SPACE OR EQUIPMENT. SECTION SECTIONS
 802.3 AND 802.3.2.
 ****RESPONSE NOTED, BUT THE CONDENSATE FROM THE COOLER
 IS STILL INDICATED AS DRAINING INTO A FLOOR SINK, AND
 SAFE WASTES ARE NOT APPROVED. EACH FLOOR SINK SHALL BE
 INDIVIDUALLY CONNECTED TO THE VENTED LINE AND HAVE ITS
 OWN TRAP. SECTIONS 901.2.1 AND 1002.1.
 ******RESPONSE NOTED, BUT INDICATE THE TYPE OF FIXTURE
 DRAINING INTO THE '2" IW W/AIR GAP'. THE DRAIN
 CONNECTING TO THE MOP SINK DRAIN AS SHOWN IS A SAFE
 WASTE AND IS NOT APPROVED. ALL INDICREC WASTE RECEPTORS
 SHALL BE SEPARATELY TRAPPED AND CONNECT TO THE VENTED
 STACK SEPARATELY AS INDICATED IN THE PREVIOUS REVIEW.
 NO DRAIN IS INDICATED FOR THE ICE MAKER. PLEASE
 INDICATE WHERE THIS WILL BE DRAINING TO. AN INDIRECT
 WASTE RECEPTOR WILL BE REQUIRED FOR THE ICE MAKER.
 SECTION 802.
  
 10. SHT P-1 WATER HEATER DETAIL: AIR
 CHAMBERS OK
 - THERMAL EXPANSION CONTROL IS
 REQUIRED AT THE WATER HEATER. PLEASE
 INDICATE METHOD. SECTION 607.3.2.
 ****NOT ADDRESSED
 ******RESPONSE NOTED, BUT THE P/T DISCHARGE VALVE IS
 NOT APPROVED FOR THERMAL EXPANSION CONTROL. PLEASE SEE
 SECTION 504.4.
  
 11. OK
 12. OK
  
 13. GREASE INTECEPTOR SHALL BE INSPECTED
 AND SIZED BY LYNN MASSON ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HER AT (TEL)
 (561) 822- 2271, (FAX) (561) 822-2279,
 OR E-MAIL [email protected]. MUNICIPAL
 CODE SECTION 3434.
 ****WAITING FOR A RESPONSE FROM LYNN. I WILL CONTACT
 HER.
 ******A NEW 750 GAL. INTERCEPTOR IS REQUIRED PER
 ENVIRONMENTAL COMPLIANCE. SEE ATTACHED SHEET. PLEASE
 INDICATE ON PLANS. A SEPARATE PERMIT IS REQUIRED FOR
 THE GREASE INTERCEPTOR.
  
 14. OK
  
 **************NEW COMMENT**************
  
 1B. OK (PLEASE REMOVE ALL VOIDED SHEETS FROM THE ONE
 SET OF PLANS).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF REPLACED SHEETS FOR COMPARISON
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved