| 2007-02-11 17:24:48 | ** UNSAT 3ND REVIEW** |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS TWO REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH NEW INFORMATION |
| | FOR REVIEW OF GAS DISPENSING STATIONS, PLANS SUBMITTED |
| | AND THE FACT THAT PERMIT HAS NOT YET BEEN APPLIED FOR. |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED |
| | FOR "PLAN REVIEW" ONLY ONCE AGAIN AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | PLEASE KNOW THAT SINCE APPLICATION FOR PERMIT HAS NOT |
| | YET BEEN MADE AND THE STATE OF FLORIDA HAS ADOPTED NEW |
| | CODES SINCE THE LAST REVIEW, PLEASE SEE PLANS WILL NOW |
| | NEED TO BE REVISED TO INDICATE THE NEW CODES AND |
| | REVISED FOR ALL NEW DESIGNS UNDER THE NEW CODES. PLEASE |
| | SEE NOTES ON PREVIOUS REVIEWS WHICH MENTION THAT PLANS |
| | HAD NOT YET BEEN SUBMITTED FOR PERMIT. PLEASE THE STATE |
| | HAS NOW ADOPTED THE 2005 NFPA-70 AND THE 2006 REVISIONS |
| | TO THE 2004 FBC FOR ALL TRADES. |
| | |
| | 2) NOTE: PLEASE SEE VALUATION FOR COMPLETE SCOPE OF |
| | SHALL BE ADJUSTED FOR ALL LABOR AND MATERIALS, EVEN IF |
| | ANY MATERIALS ARE OWNER SUPPLIED. FBC 108.3. |
| | VALUE CAN NOT BE VERIFIED UNTIL APPLICATION FOR PERMIT |
| | IS MADE. |
| | |
| | 3) NOTE: THERE WAS NO RESPONSE TO THIS; THE G-1 PLAN(S) |
| | DO NOT SHOW ALL LOCATIONS. |
| | PLEASE CLEARLY LABEL AND IDENTIFY ALL CLASS/DIVISION |
| | LOCATIONS PER NEC 514, NFPA-30. |
| | PLEASE PROVIDE LAYOUT FOR DISTANCES OF DISCONNECTING |
| | MEANS FOR PUMPS ETC. |
| | THIS WAS NOTED ON PREVIOUS REVIEW. |
| | |
| | 4) NOTE: PLEASE SHOW A DETAIL FOR THE DISCONNECTING |
| | MEANS. A MUSHROOM BUTTON IS SHOWN, HOWEVER NO |
| | INFORMATION/DETAIL IS SHOWN ON HOW THIS WILL BE TIED |
| | INTO THE BRANCH CIRCUITS REQUIRED TO BE SHUT DOWN. |
| | 514.11 |
| | PLEASE SEE 514 IN HAND BOOK AS EXAMPLES ARE SHOWN. |
| | |
| | 5) NOTE: PLEASE SEE THIS COMMENT HAS BEEN MADE ON ALL |
| | THREE REVIEWS AND NO CHANGE HAS BEEN MADE TO RISER |
| | PERTAINING TO THIS???? |
| | PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR" IS BEING |
| | SHOWN BEFORE THE FIRST MEANS OF DISCONNECT FOR THE |
| | SERVICE. PLEASE SEE 250.6, 250.24B, AS THIS IS ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | |
| | |
| | |
| | 6) NOTE: PLEASE SEE THE OLD NON-VALID SEAL IS STILL |
| | BEING USED ON SOME SHEETS WHICH ARE STILL IN SETS. |
| | PLEASE SEE SOME OF THE OLD SHEETS WERE LEFT IN SETS |
| | WITH OUT INSERTING NEW SHEETS FOR THESE. |
| | PLEASE SEE NOTE AS STATED IN PREVIOUS REVIEW. |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | * PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.001. |
| | MUST CONTAIN THE WORDING "LICENSE" AND MAY NO LONGER |
| | CONTAIN THE WORDING "CERTIFICATE". |
| | PLEASE ALSO KNOW, THIS IS REQUIRED FOR ALL SHEETS AND |
| | FOR ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 7) NOTE: PLEASE SEE FLORIDA STATUE 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE |
| | KNOW, ONE COPY OF PLANS SUBMITTED IS BEING RETAINED. |
| | THE 4X FEE HAS NOT BEEN ASSESSED AS LEGAL PERMIT |
| | APPLICATION HAS NOT BEEN MADE. |
| | |
| | 8) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS |
| | HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY |
| | 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES |
| | ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL |
| | REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP |
| | GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE |
| | PLANS SUBMITTED. |
| | PLEASE INDICATE HOW THE GENERATOR WILL BE CONNECTED |
| | INTO THE BUILDINGS MAIN ELECTRICAL SERVICE. |
| | PLEASE SEE 701 AND 2002 NFPA-110 |
| | PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER |
| | NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME |
| | MOVER ETC ETC. |
| | PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 |
| | ETC |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |