| Date |
Text |
| 2007-03-22 12:56:09 | ****CORRECTIONS**** |
| | ****PLAN CHECK ONLY, NOT A PERMIT |
| | APPLICATION**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | COMMENTS FROM PREVIOUS LISTS, NOT |
| | ADDRESSED |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713. |
| | |
| | 2.)IMPACT FEES MAY BE OWED TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025. |
| | |
| | **10/10, CONFIRMED WITH PALM BEACH COUNTY, IMPACT FEE |
| | ASSESSMENT REQUIRED*** |
| | |
| | 3.)DECLARE THE LEVEL OF ALTERATION, |
| | FBC EB 301. |
| | |
| | 4.)DECLARE OCCUPANCY FBC309, MINIMUM |
| | BUILDING TYPE FBC6.TYPE V WAS |
| | DECLARED, NEED TO ALSO DECLARE A OR B. |
| | |
| | M AND B WAS DECLARED.PROVIDE SF AREA FOR EACH |
| | OCCUPANCY SO THAT OCCUPANT LOAD CAN BE DETERMINED. |
| | |
| | 5.)DECLARE AN OCCUPANT LOAD, FBC10. |
| | |
| | HOW HAVE YOU ARRIVED AT AN OCCUPANT LOAD OF 16, 1000/8 |
| | X 1980?SEE FBC1004.1, MUST USE EITHER DESIGN LOAD OR |
| | BASED ON FBC TABLE 1004.1.2, WHICHEVER IS GREATER.M |
| | AND B HAVE DIFFERENT OCCUPANT LOADS.SEE FBC309; IT |
| | APPEARS THAT HIS IS M OCCUPANCY, NOT B.PROVIDE MORE |
| | INFORMATION IN REGARDS TO THE USE OF THIS BUILDING TO |
| | JUSTIFY THE B OCCUPANCY CLASSIFICATION. |
| | |
| | 6.)ADDRESSED. |
| | |
| | 7.)PRODUCT APPROVALS REQUIRED FOR THE |
| | STOREFRONT AND DOORS.FLORIDA STATE OR |
| | LOCAL PRODUCT APPROVALS REQUIRED |
| | FAC9B72. WWW.FLORIDABUILDING.ORG |
| | |
| | 8.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD, |
| | FBC*106.3.3. |
| | |
| | 10.)PROVIDE WIND DESIGN CRITERIA |
| | FBC1603.1.4.THIS WAS PROVIDED BUT PLEASE CLARIFY HOW |
| | YOU HAVE ARRIVED AT A -.25 INTERNAL PRESSURE |
| | COEFFICIENT.THIS MAY BE DONE IN A SIGNED, SEALED |
| | LETTER (DOES NOT HAVE TO BE ON THE PLAN).THIS APPEARS |
| | TO BE A FULLY ENCLOSED BUILDING, AND TYPICALLY THE |
| | INTERNAL PRESSURE COEFFICIENT IS -.18.IT IS |
| | ACCEPTABLE TO EXCEED MINIMUM CODE REQUIREMENTS BUT I AM |
| | REQUESTING CLARIFICATION. |
| | |
| | 11-15.)ADDRESSED. |
| | |
| | 16.)PROVIDE A BREAKDOWN OF COSTS TO |
| | DETERMINE WHETHER OR NOT ENERGY CALCS |
| | ARE REQUIRED AND TO CONFIRM VALUATION |
| | PROVIDED.SEE FBC 13-101.1, FBC13-202, |
| | FBC EB708.1. |
| | |
| | PROVIDE ENERGY CALCS, INCREASE IN |
| | CONDITIONED FLOOR AREA.SEE |
| | FBC13-1-1.1.2, DEFINITION OF ADDITION |
| | FBC13-202. |
| | |
| | THE BREAKDOWN OF COSTS WAS PROVIDED, BUT NO ENERGY |
| | CALCS WERE SUBMITTED. |
| | |
| | 17.)PROVIDE ENERGY CALCS AND SIGN IN |
| | ALL APPLICABLE PLACES, INCLUDING THE |
| | OWNER/AGENT LINE FBC13-103.1. |
| | |
| | 18-19.)ADDRESSED. |
| | |
| | 20.)M2 WAS REVISED AS PER PREVIOUS |
| | LIST, BUT STILL REFERS TO HIGH VELOCITY. |
| | CITY OF WEST PALM BEACH IS NOT IN THE |
| | HIGH VELOCITY ZONE. |
| | |
| | THE CHART IS FROM HVHZ, PLEASE USE THE APPROPRIATE |
| | CHART FROM FBC TABLE 1509.7.ALSO, THERE IS A TYPE ON |
| | LINE 3 (27). |
| | |
| | 21.)WHEN RESUBMITTING, PLEASE REMOVE |
| | OLD SHEETS. |
| | |
| | BUT PLEASE PROVIDE THEM FOR REFERENCE. |
| | |
| | 22.)N/A |
| | |
| | 23.)IT APPEARS THAT MANY COMMENTS WERE |
| | NOT ADDRESSED.TO EXPEDITE PLAN REVIEW, |
| | PLEASE INCLUDE A RESPONSE LETTER |
| | INDICATING HOW AND WHERE EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | PLEASE SUBMIT BOTH THE OLD SHEETS AND A RESPONSE LETTER |
| | WHEN RESUBMITTING.FAILURE TO DO SO REQUIRES A |
| | COMPLETELY NEW PLAN REVIEW AND INCREASES THE |
| | POSSIBILITY OF NEW COMMENTS. |
| | |
| | 24.)NEW COMMENT; EDGE PROTECTION REQUIRED |
| | FBC11-4.8.7. |
| | |
| | 25.)SHEET 2, SHOW SIDEWALK WIDTH (ACCESSIBLE ROUTE |
| | FBC11-4.1). |
| | |
| | 26.)ALL CHANGES ARE TO BE CLOUDED. |
| | |