Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop B
Sequence Number 3
Notes
Date Text
2007-03-22 12:56:09****CORRECTIONS****
 ****PLAN CHECK ONLY, NOT A PERMIT
 APPLICATION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LISTS, NOT
 ADDRESSED
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)IMPACT FEES MAY BE OWED TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025.
  
 **10/10, CONFIRMED WITH PALM BEACH COUNTY, IMPACT FEE
 ASSESSMENT REQUIRED***
  
 3.)DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.)DECLARE OCCUPANCY FBC309, MINIMUM
 BUILDING TYPE FBC6.TYPE V WAS
 DECLARED, NEED TO ALSO DECLARE A OR B.
  
 M AND B WAS DECLARED.PROVIDE SF AREA FOR EACH
 OCCUPANCY SO THAT OCCUPANT LOAD CAN BE DETERMINED.
  
 5.)DECLARE AN OCCUPANT LOAD, FBC10.
  
 HOW HAVE YOU ARRIVED AT AN OCCUPANT LOAD OF 16, 1000/8
 X 1980?SEE FBC1004.1, MUST USE EITHER DESIGN LOAD OR
 BASED ON FBC TABLE 1004.1.2, WHICHEVER IS GREATER.M
 AND B HAVE DIFFERENT OCCUPANT LOADS.SEE FBC309; IT
 APPEARS THAT HIS IS M OCCUPANCY, NOT B.PROVIDE MORE
 INFORMATION IN REGARDS TO THE USE OF THIS BUILDING TO
 JUSTIFY THE B OCCUPANCY CLASSIFICATION.
  
 6.)ADDRESSED.
  
 7.)PRODUCT APPROVALS REQUIRED FOR THE
 STOREFRONT AND DOORS.FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72. WWW.FLORIDABUILDING.ORG
  
 8.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 10.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.THIS WAS PROVIDED BUT PLEASE CLARIFY HOW
 YOU HAVE ARRIVED AT A -.25 INTERNAL PRESSURE
 COEFFICIENT.THIS MAY BE DONE IN A SIGNED, SEALED
 LETTER (DOES NOT HAVE TO BE ON THE PLAN).THIS APPEARS
 TO BE A FULLY ENCLOSED BUILDING, AND TYPICALLY THE
 INTERNAL PRESSURE COEFFICIENT IS -.18.IT IS
 ACCEPTABLE TO EXCEED MINIMUM CODE REQUIREMENTS BUT I AM
 REQUESTING CLARIFICATION.
  
 11-15.)ADDRESSED.
  
 16.)PROVIDE A BREAKDOWN OF COSTS TO
 DETERMINE WHETHER OR NOT ENERGY CALCS
 ARE REQUIRED AND TO CONFIRM VALUATION
 PROVIDED.SEE FBC 13-101.1, FBC13-202,
 FBC EB708.1.
  
 PROVIDE ENERGY CALCS, INCREASE IN
 CONDITIONED FLOOR AREA.SEE
 FBC13-1-1.1.2, DEFINITION OF ADDITION
 FBC13-202.
  
 THE BREAKDOWN OF COSTS WAS PROVIDED, BUT NO ENERGY
 CALCS WERE SUBMITTED.
  
 17.)PROVIDE ENERGY CALCS AND SIGN IN
 ALL APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 18-19.)ADDRESSED.
  
 20.)M2 WAS REVISED AS PER PREVIOUS
 LIST, BUT STILL REFERS TO HIGH VELOCITY.
 CITY OF WEST PALM BEACH IS NOT IN THE
 HIGH VELOCITY ZONE.
  
 THE CHART IS FROM HVHZ, PLEASE USE THE APPROPRIATE
 CHART FROM FBC TABLE 1509.7.ALSO, THERE IS A TYPE ON
 LINE 3 (27).
  
 21.)WHEN RESUBMITTING, PLEASE REMOVE
 OLD SHEETS.
  
 BUT PLEASE PROVIDE THEM FOR REFERENCE.
  
 22.)N/A
  
 23.)IT APPEARS THAT MANY COMMENTS WERE
 NOT ADDRESSED.TO EXPEDITE PLAN REVIEW,
 PLEASE INCLUDE A RESPONSE LETTER
 INDICATING HOW AND WHERE EACH ITEM WAS
 ADDRESSED.
  
 PLEASE SUBMIT BOTH THE OLD SHEETS AND A RESPONSE LETTER
 WHEN RESUBMITTING.FAILURE TO DO SO REQUIRES A
 COMPLETELY NEW PLAN REVIEW AND INCREASES THE
 POSSIBILITY OF NEW COMMENTS.
  
 24.)NEW COMMENT; EDGE PROTECTION REQUIRED
 FBC11-4.8.7.
  
 25.)SHEET 2, SHOW SIDEWALK WIDTH (ACCESSIBLE ROUTE
 FBC11-4.1).
  
 26.)ALL CHANGES ARE TO BE CLOUDED.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved