Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-12 14:06:09******* UNSAT 2ND REVIEW********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLYONCE AGAIN
 AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE VALUATION FOR COMPLETE
 SCOPE OF SHALL BE ADJUSTED FOR ALL LABOR
 AND MATERIALS, EVEN IF ANY MATERIALS ARE
 OWNER SUPPLIED. FBC 108.3.
 VALUE SHOWN SEEMS LOW FOR SCOPE OF WORK
 SHOWN ON PLANS.
 PLEASE ADJUST.
  
 *** PLEASE SEE MANY OF THE SAME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS ADDED TO THE BOTTOM OF REVIEW.
  
 1) NOTE: NO, SAME COMMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL CURRENT CODES
 ADOPTED BY THE STATE SHALL BE REFERENCE
 ON PLANS. 2002, NFPA-70, 2004 FBC ETC.
 PLEASE ALSO SEE ALL CURRENT CODES.
 PLEASE ALSO SEE PLANS INDICATE "PALM
 BEACH COUNTY BUILDING DEPARTMENT".
 PLEASE KNOW, THIS SCOPE OF WORK IS DONE
 IN THE "CITY OF WEST PALM BEACH".
  
 2) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLEARLY LABEL AND
 IDENTIFY ALL CLASS/DIVISION LOCATIONS
 PER NEC 514, NFPA-30.
 PLEASE PROVIDE LAYOUT FOR DISTANES OF DISCONNECTING
 MEANS FOR PUMPS ETC.
  
 3) NOTE:NO, SAME NOTE .
  
 ** PREVIOUSREVIEW NOTE **
 PLEASE SHOW A DETAIL FOR THE DISCONNECTING MEANS. A
 MUSHROOM BUTTON
 IS SHOWN, HOWEVER NO INFORMATION/DETAIL
 IS SHOWN ON HOW THIS WILL BE TIED INTO
 THE BRANCH CIRCUITS REQUIRED TO BE SHUT
 DOWN.
 514.11
 PLEASE SEE 514 IN HAND BOOK AS EXAMPLES
 ARE SHOWN.
  
 4) NOTE: OK.
  
 5) NOTE: NO, PLEASE STILL SEE PANEL "C".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRLEATE PANEL SIZES,
 CIRCUITING ETC.
 24 CIR 225A ?? PLEASE VERIFY AS 225A
 PANELS ARE NOT COMMON FOR 24 CIRCUITS?
 PLEASE SEE PANELS SHOWN AS 30 CIRCUIT,
 YET RISER SHOWS THESE AS 42 CIRCUIT?
  
 6) NOTE: NO, PLEASE SEE THIS POSSIBLE MISPRINT, BELOW
 PANEL "A", AS "FEEDER, 2001"?
  
 ** PREIVOUS REVIEW NOTE **
 PLEASE SEE PANEL "A" SHOWN AS
 200I)??
 PLEASE CLARIFY THIS.
 215.5
  
 7) NOTE: OK.
  
 8) NOTE: NO, SAME NOTE, STILL BEING SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT FOR
 THE SERVICE. PLEASE SEE 250.6, 250.24B,
 AS THIS IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 9) NOTE: NO, SAME NOTE. PLANS MENTIONS CONTRACTOR TO
 VERIFY, HOWEVER THIS IS THE RESPONSIBILITY OF THE
 DESIGNER OF RECORD AND IS REQUIRED ON PLANS AT THIS
 TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE SIZE OF THE
 EXISITNG OR NEW SEC'S ON RISER.
 215.5
 CAN NOT VERIFY AT THIS TIME.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE:NO, SAME NOTE. PLEASE ALSO SEE NEW NOTES FOR
 SEAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS PER FAC
 61G15-23.002, FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION #.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
  
  
 ****** NEW NOTES *****
  
 15) NOTE: PLEASE SEE SEAL BEING USED ON ALL SHEETS FOR
 NEW PLANS SUBMITTED IS NO LONGER VALID WITH TEH STATE
 OF FLORIDA PER FLORIDA ADMINSITRATIVE CODE
 61G15-23.001.
 PLEASE KNOW, THIS WAS NOT A COMMENT ON PREVIOUS REVIEW
 AS SHEETS ARE BEING SEALED WITH A COMPLETELY DIFFERENT
 SEAL.
 MUST CONTAIN THE WORDING "LICENSE" AND MAY NO LONGER
 CONTAIN THE OWRDING "CERTIFICATE".
 PLEASE ALSO KNOW, THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 16) NOTE:PLEASE SEE FLORIDA STATUE 553.80(2)(B) WITH
 RESPECT TO REPEAT COPMMENTS FOR CODE COMPLIANCE. PLEASE
 KNOW, ONE COPY OF PLANS SUBMITTED ARE BEING RETAINED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  