| Date |
Text |
| 2006-10-12 14:06:09 | ******* UNSAT 2ND REVIEW******** |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" ONLYONCE AGAIN |
| | AND HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | |
| | ** PLEASE SEE VALUATION FOR COMPLETE |
| | SCOPE OF SHALL BE ADJUSTED FOR ALL LABOR |
| | AND MATERIALS, EVEN IF ANY MATERIALS ARE |
| | OWNER SUPPLIED. FBC 108.3. |
| | VALUE SHOWN SEEMS LOW FOR SCOPE OF WORK |
| | SHOWN ON PLANS. |
| | PLEASE ADJUST. |
| | |
| | *** PLEASE SEE MANY OF THE SAME COMMENTS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS ADDED TO THE BOTTOM OF REVIEW. |
| | |
| | 1) NOTE: NO, SAME COMMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ALL CURRENT CODES |
| | ADOPTED BY THE STATE SHALL BE REFERENCE |
| | ON PLANS. 2002, NFPA-70, 2004 FBC ETC. |
| | PLEASE ALSO SEE ALL CURRENT CODES. |
| | PLEASE ALSO SEE PLANS INDICATE "PALM |
| | BEACH COUNTY BUILDING DEPARTMENT". |
| | PLEASE KNOW, THIS SCOPE OF WORK IS DONE |
| | IN THE "CITY OF WEST PALM BEACH". |
| | |
| | 2) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLEARLY LABEL AND |
| | IDENTIFY ALL CLASS/DIVISION LOCATIONS |
| | PER NEC 514, NFPA-30. |
| | PLEASE PROVIDE LAYOUT FOR DISTANES OF DISCONNECTING |
| | MEANS FOR PUMPS ETC. |
| | |
| | 3) NOTE:NO, SAME NOTE . |
| | |
| | ** PREVIOUSREVIEW NOTE ** |
| | PLEASE SHOW A DETAIL FOR THE DISCONNECTING MEANS. A |
| | MUSHROOM BUTTON |
| | IS SHOWN, HOWEVER NO INFORMATION/DETAIL |
| | IS SHOWN ON HOW THIS WILL BE TIED INTO |
| | THE BRANCH CIRCUITS REQUIRED TO BE SHUT |
| | DOWN. |
| | 514.11 |
| | PLEASE SEE 514 IN HAND BOOK AS EXAMPLES |
| | ARE SHOWN. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: NO, PLEASE STILL SEE PANEL "C". |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRLEATE PANEL SIZES, |
| | CIRCUITING ETC. |
| | 24 CIR 225A ?? PLEASE VERIFY AS 225A |
| | PANELS ARE NOT COMMON FOR 24 CIRCUITS? |
| | PLEASE SEE PANELS SHOWN AS 30 CIRCUIT, |
| | YET RISER SHOWS THESE AS 42 CIRCUIT? |
| | |
| | 6) NOTE: NO, PLEASE SEE THIS POSSIBLE MISPRINT, BELOW |
| | PANEL "A", AS "FEEDER, 2001"? |
| | |
| | ** PREIVOUS REVIEW NOTE ** |
| | PLEASE SEE PANEL "A" SHOWN AS |
| | 200I)?? |
| | PLEASE CLARIFY THIS. |
| | 215.5 |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: NO, SAME NOTE, STILL BEING SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" IS BEING SHOWN |
| | BEFORE THE FIRST MEANS OF DISCONNECT FOR |
| | THE SERVICE. PLEASE SEE 250.6, 250.24B, |
| | AS THIS IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 9) NOTE: NO, SAME NOTE. PLANS MENTIONS CONTRACTOR TO |
| | VERIFY, HOWEVER THIS IS THE RESPONSIBILITY OF THE |
| | DESIGNER OF RECORD AND IS REQUIRED ON PLANS AT THIS |
| | TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE SIZE OF THE |
| | EXISITNG OR NEW SEC'S ON RISER. |
| | 215.5 |
| | CAN NOT VERIFY AT THIS TIME. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE:NO, SAME NOTE. PLEASE ALSO SEE NEW NOTES FOR |
| | SEAL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS PER FAC |
| | 61G15-23.002, FS 471.023. |
| | MISSING CERTIFICATE OF AUTHORIZATION #. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | |
| | |
| | ****** NEW NOTES ***** |
| | |
| | 15) NOTE: PLEASE SEE SEAL BEING USED ON ALL SHEETS FOR |
| | NEW PLANS SUBMITTED IS NO LONGER VALID WITH TEH STATE |
| | OF FLORIDA PER FLORIDA ADMINSITRATIVE CODE |
| | 61G15-23.001. |
| | PLEASE KNOW, THIS WAS NOT A COMMENT ON PREVIOUS REVIEW |
| | AS SHEETS ARE BEING SEALED WITH A COMPLETELY DIFFERENT |
| | SEAL. |
| | MUST CONTAIN THE WORDING "LICENSE" AND MAY NO LONGER |
| | CONTAIN THE OWRDING "CERTIFICATE". |
| | PLEASE ALSO KNOW, THIS IS REQUIRED FOR ALL SHEETS AND |
| | FOR ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 16) NOTE:PLEASE SEE FLORIDA STATUE 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COPMMENTS FOR CODE COMPLIANCE. PLEASE |
| | KNOW, ONE COPY OF PLANS SUBMITTED ARE BEING RETAINED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |