| 2006-10-06 00:00:00 | ****CORRECTIONS**** |
| | ****PLAN CHECK ONLY, NOT A PERMIT |
| | APPLICATION**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | COMMENTS FROM PREVIOUS LIST, NOT |
| | ADDRESSED |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713. |
| | |
| | 2.)IMPACT FEES MAY BE OWED TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025.PENDING RETURN |
| | TELEPHONE CALL FROM PBC. |
| | |
| | **10/10, CONFIRMED WITH PALM BEACH COUNTY, IMPACT FEE |
| | ASSESSMENT REQUIRED*** |
| | |
| | 3.)DECLARE THE LEVEL OF ALTERATION, |
| | FBC EB 301. |
| | |
| | 4.)DECLARE OCCUPANCY FBC309, MINIMUM |
| | BUILDING TYPE FBC6.TYPE V WAS |
| | DECLARED, NEED TO ALSO DECLARE A OR B. |
| | |
| | 5.)DECLARE AN OCCUPANT LOAD, FBC10. |
| | |
| | 6.)THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR EGN, INC. IS TO BE ON EACH |
| | SHEET, FAC61G15-23.002. |
| | |
| | 7.)PRODUCT APPROVALS REQUIRED FOR THE |
| | STOREFRONT AND DOORS.FLORIDA STATE OR |
| | LOCAL PRODUCT APPROVALS REQUIRED |
| | FAC9B72. WWW.FLORIDABUILDING.ORG |
| | |
| | 8.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD, |
| | FBC*106.3.3. |
| | |
| | 10.)PROVIDE WIND DESIGN CRITERIA |
| | FBC1603.1.4. |
| | |
| | 11.)EXIT ACCESS SHALL NOT GO THROUGH |
| | STORAGE ROOMS, FBC1013.2. |
| | |
| | 12.)ADDRESSED. |
| | |
| | 13.)PARKING IS NOT SHOWN ON THE PLAN. |
| | IF PARKING IS PROVIDED, ACCESSIBLE |
| | PARKING IS REQUIRED FBC11-4.6.SEE |
| | ATTACHED DETAIL.PLEASE PROVIDE |
| | ACCESSIBLE PARKING DETAIL, SHOW |
| | LOCATION. |
| | |
| | 14.)ADDRESSED. |
| | |
| | 15.)PLANS INDICATE THAT THE EXISTING |
| | MANSARD IS TO BE RESURFACED A3.ROOF |
| | PERMIT REQUIRED. |
| | |
| | 16.)PROVIDE A BREAKDOWN OF COSTS TO |
| | DETERMINE WHETHER OR NOT ENERGY CALCS |
| | ARE REQUIRED AND TO CONFIRM VALUATION |
| | PROVIDED.SEE FBC 13-101.1, FBC13-202, |
| | FBC EB708.1. |
| | |
| | PROVIDE ENERGY CALCS, INCREASE IN |
| | CONDITIONED FLOOR AREA.SEE |
| | FBC13-1-1.1.2, DEFINITION OF ADDITION |
| | FBC13-202. |
| | |
| | 17.)PROVIDE ENERGY CALCS AND SIGN IN |
| | ALL APPLICABLE PLACES, INCLUDING THE |
| | OWNER/AGENT LINE FBC13-103.1. |
| | |
| | 18.)SPECIFY INTERIOR FINISH |
| | CLASSIFICATION, FBC TABLE 803.5. |
| | |
| | 19.)THERE IS A NOTE ON M2 STATING THAT |
| | EQUIPMENT IS TO BE ANCHORED PER FBC 15 |
| | AND 16 AND TO WITHSTAND 146MPH.SPECIFY ANCHORING. |
| | |
| | 20.)M2 WAS REVISED AS PER PREVIOUS |
| | LIST, BUT STILL REFERS TO HIGH VELOCITY. |
| | CITY OF WEST PALM BEACH IS NOT IN THE |
| | HIGH VELOCITY ZONE. |
| | |
| | NEW COMMENTS: |
| | |
| | 21.)WHEN RESUBMITTING, PLEASE REMOVE |
| | OLD SHEETS. |
| | |
| | 22.)PLEASE NOTE THAT THE "CANOPY" |
| | SHOULD BE INCLUDED IN BUILDING AREA, SEE DEFINITIONS, |
| | FBC5. |
| | |
| | 23.)IT APPEARS THAT MANY COMMENTS WERE |
| | NOT ADDRESSED.TO EXPEDITE PLAN REVIEW, |
| | PLEASE INCLUDE A RESPONSE LETTER |
| | INDICATING HOW AND WHERE EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU |
| | NEED ASSISTANCE WITH ANY OF THE ABOVE. |
| | |