2009-10-26 08:39:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE THE RHEEM "UNIT TIE DOWN INSTRUCTIONS"
 (ST-A1024-01). IT STATES "MINIMUM 18 GA. X 1" WIDE
 GALV. STEEL STRAP (G90) OR EQUIVALENT (TYPE. 1 EACH
 CORNER)." CURB INSTALLATION DETAILS ALSO DO NOT SPECIFY
 A SPECIFIC PRODUCT.
  
 THE TEXT SPECIFIES A STRAP, BUT THE GRAPHIC DEPICTS AN
 ANGLE. I WAS UNABLE TO LOCATE A HURRICANE CONNECTOR
 WHICH MEETS THIS DESCRIPTION. PLEASE SPECIFY WHICH
 HURRICANE CONNECTOR WOULD BE ACCEPTABLE FOR EACH DETAIL
 TO BE USED ON THIS JOB.
  
 2. PLEASE SEE PAGE 11 OF THE SIMPSON STRONG-TIE
 CONNECTOR WOOD CONSTRUCTION CONNECTOR CATALOG:
 HTTP://WWW.STRONGTIE.COM/LITERATURE/C-2009.HTML
  
 OR THE USP CONNECTOR CATALOG "CORROSION INFORMATION":
 HTTP://WWW.USPCONNECTORS.COM/PDF-FULL-LINE-2009/CATEGOR
 IES/CORROSION55.PDF
  
  
 G90 HAS BEEN SPECIFIED, BUT THE CONNECTOR MANUFACTURERS
 RECOMMEND THAT G90 FINISH BE USED ONLY IN LOW EXPOSURE
 STRUCTURAL APPLICATIONS. IF THE CONNECTOR SPECIFIED IN
 RESPONSE TO COMMENT #1 IS OF A G90 FINISH, PLEASE HAVE
 BOTH THE MANUFACTURER'S ENGINEER AND THE EOR FOR THE
 PROJECT ACKNOWLEDGE THIS INFORMATION.
  
 3. SPECIFY THE LOCATION OF HURRICANE ANGLE
 INSTALLATION. THE DRAWING APPEARS TO SHOW ANGLES AT
 EACH CORNER OF THE LONG SIDE OF THE UNIT AND ONE IN THE
 CENTER (WITH A NOTE STATING THAT CENTER TO CENTER NOT
 TO EXCEED 48"), BUT NONE ON THE SHORT SIDE. IF
 INSTALLED AS DEPICTED GRAPHICALLY, THE UNIT WILL NOT
 RESIST WIND FROM ALL DIRECTIONS. FBC1609.
  
 4. PROVIDE EITHER A SHOP DRAWING REVIEW STAMP FROM THE
 ENGINEER OF RECORD OR A SIGNED AND SEALED LETTER
 STATING THAT HE HAS REVIEWED THE STAND AND CURB PRODUCT
 APPROVALS, INSTALLATION INSTRUCTIONS, AND CERTIFICATION
 FOR WIND RESISTANCE. FBC*106.
  
 5. PLEASE CLARIFY METHOD OF INSTALLATION. THE PLAN
 STATES THAT THE UNITS WILL BE INSTALLED ON ROOF CURBS.
 ROOF CURB INSTALLATION DETAILS WERE SUBMITTED AND A
 ROOF STAND DETAIL AND PRODUCT APPROVAL WERE SUBMITTED.
 ARE THE UNITS TO BE INSTALLED ON A CURB, STAND, OR ONE
 OF EACH? ONE OF THE DETAILS IS FOR A CURB WITH AN
 ATTACHMENT, DOES THAT DETAIL ALSO APPLY TO THIS JOB?
 PLEASE REMOVE DETAILS WHICH DO NOT PERTAIN TO THIS JOB,
 AND REVISE THE DETAILS WHICH DO PERTAIN TO THIS JOB TO
 SPECIFY HURRICANE ANCHORS.
  
 6. THIS ISSUE MAY BE RESOLVED VIA EMAIL (WITH THE
 EXCEPTION OF ITEM 4). THE ENGINEER (EITHER EOR OR RHEEM
 ENGINEER) CAN SPECIFY HURRICANE STRAPS OR ANGLES VIA
 EMAIL. PRIOR TO ISSUANCE, THE SHOP DRAWING REVIEW STAMP
 OR LETTER FROM EOR IS REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE.
  
  
  
  