Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-19 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODES
  
 1. SURVEY SHEET, PER SURVEYORS
 CERTIFICATION STATEMENT, "NOT VALID
 WITHOUT THE SIGNATURE AND THE ORIGINAL
 RAISED SEAL OF A LICENSED SURVEYOR AND
 MAPER. NO SIGNATURE OR SEAL ON PLANS.
 FAC 61G17-6.003(2)(C) & FS 472.025.
  
 2. ALL ARCHITECTURAL & PM&E SHEETS.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. NO CERTIFICATE
 OF AUTHORIZATION SHOWN. FAC
 61G15-23.002(2) AND FS 471.025.
  
 3. SHT A-1A. FLOOR PLAN, A DRINKING
 FOUNTAIN IS REQUIRED PER TABLE 403.1.
  
 4. SHT A-1A. SCOPE OF WORK, PLEASE
 INDICATE DESIGN BY FBC-2004, AND CITY
 WEST PALM BEACH UNDER SCOPE OF WORK.
 (NOT PALM BEACH COUNTY).
  
 5. SHT A-1A. UNDER SCOPE OF WORK -
 PROPOSED LINE 1) INDICATES (SEE SHEET
 A-1). SHT A-1 HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 6. SHT A-1B. HANDICAPPED RESTROOM NOTES:
 GRAB BARS INDICATED AS 32-1/2 TO 33"
 AFF. SECTION 11-4.16.4 REQUIRES GRAB
 BARS TO BE 33" TO 36". (FIG 29). -
 TOILET PAPER DISPENSER IS INDICATED AS
 17" AFF. MINIMUM 19" PER 11-4.16.6. -
 ALSO SHOW THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
  
 7. SHT A-1B. INTERIOR ELEVATIONS SHOW
 THE FOLLOWING FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
  
 8. SHT P-1 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE ICE MAKER
 AND SHALL BE LOCATED NEAR THE FIXTURE IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 SECTION 604.9, PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 9. SHT P-1 SANITARY RISER DIAGRAM AND
 FLOOR PLAN, FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB IS REQUIRED FOR
 INDIRECT WASTE. FLOOR SINKS SHALL BE
 LOCATED AS TO NOT BE A TRIPPING HAZARD
 AND SHALL BE LOCATED UNDER THE COUNTER
 SPACE OR EQUIPMENT. SECTION SECTIONS
 802.3 AND 802.3.2.
  
 10. SHT P-1 WATER HEATER DETAIL: AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 DETAIL. - THERMAL EXPANSION CONTROL IS
 REQUIRED AT THE WATER HEATER. PLEASE
 INDICATE METHOD. SECTION 607.3.2.
  
 11. SHT P-1 HANDICAPPED RESTROOM NOTES:
 (SEE COMMENT NUMBER 6).
  
 12 SHT P-1 NOTES: FIXTURES TO COMPLY
 WITH CITY OF WEST PALM BEACH AND
 FBC-2004 CHAPTER 11 CODE NOT PALM BEACH
 COUNTY CODES.
  
 13. GREASE INTECEPTOR SHALL BE INSPECTED
 AND SIZED BY LYNN MASSON ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HER AT (TEL)
 (561) 822- 2271, (FAX) (561) 822-2279,
 OR E-MAIL [email protected]. MUNICIPAL
 CODE SECTION 3434.
  
 14. AN RPZV BACKFLOW PREVENTOR IS
 REQUIRED. SECTION 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved