2006-06-09 00:00:00DENIED:
  
 1.PLANS ARE TO BE SUBMITTED TO DERM
 FOR APPROVAL.PLANS MAY BE SUBMITTED AT
 3323 BELVEDERE RD. BUILDING #502 WEST
 PALM BEACH, FLORIDA. IF YOU NEED FURTHER
 INFORMATION FROM DERM, PLEASE CONTACT
 CHIP GREEN AT (561)233-2400.
  
 2.PLEASE SUBMIT PLANS WITH DERM'S
 APPROVAL.
  
 3.PLAN SHEET M2 THE EXHAUST FAN DETAIL
 INDICATES THE ROOF CURB AS BEING 6"
 ABOVE THE ROOF.PER 2004 FBC 1509.7,
 CURBS SHALL BE A MINIMUM OF 8" ABOVE THE
 ROOF SURFACE.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED IN ACCORDANCE WITH 2004 FMC
 606.2.1 & 606.2.2.
  
 5.ADDITIONAL PERMITS REQUIRED FOR FUEL
 & WALK-IN COOLERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  