| Plan Review Notes For Permit 06040955 |
| Permit Number |
06040955 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-09 00:00:00 | DENIED: | | | | | | 1.PLANS ARE TO BE SUBMITTED TO DERM | | | FOR APPROVAL.PLANS MAY BE SUBMITTED AT | | | 3323 BELVEDERE RD. BUILDING #502 WEST | | | PALM BEACH, FLORIDA. IF YOU NEED FURTHER | | | INFORMATION FROM DERM, PLEASE CONTACT | | | CHIP GREEN AT (561)233-2400. | | | | | | 2.PLEASE SUBMIT PLANS WITH DERM'S | | | APPROVAL. | | | | | | 3.PLAN SHEET M2 THE EXHAUST FAN DETAIL | | | INDICATES THE ROOF CURB AS BEING 6" | | | ABOVE THE ROOF.PER 2004 FBC 1509.7, | | | CURBS SHALL BE A MINIMUM OF 8" ABOVE THE | | | ROOF SURFACE. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED IN ACCORDANCE WITH 2004 FMC | | | 606.2.1 & 606.2.2. | | | | | | 5.ADDITIONAL PERMITS REQUIRED FOR FUEL | | | & WALK-IN COOLERS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | | | | | | | |
|