| Date |
Text |
| 2006-05-16 00:00:00 | ******* UNSAT ******** |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" ONLY AND |
| | HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | |
| | ** PLEASE SEE VALUATION FOR COMPLETE |
| | SCOPE OF SHALL BE ADJUSTED FOR ALL LABOR |
| | AND MATERIALS, EVEN IF ANY MATERIALS ARE |
| | OWNER SUPPLIED. FBC 108.3. |
| | VALUE SHOWN SEEMS LOW FOR SCOPE OF WORK |
| | SHOWN ON PLANS. |
| | PLEASE ADJUST. |
| | |
| | 1) NOTE: PLEASE SEE ALL CURRENT CODES |
| | ADOPTED BY THE STATE SHALL BE REFERENCE |
| | ON PLANS. 2002, NFPA-70, 2004 FBC ETC. |
| | PLEASE ALSO SEE ALL CURRENT CODES. |
| | PLEASE ALSO SEE PLANS INDICATE "PALM |
| | BEACH COUNTY BUILDING DEPARTMENT". |
| | PLEASE KNOW, THIS SCOPE OF WORK IS DONE |
| | IN THE "CITY OF WEST PALM BEACH". |
| | |
| | 2) NOTE: PLEASE CLEARLY LABEL AND |
| | IDENTIFY ALL CLASS/DIVISION LOCATIONS |
| | PER NEC 514, NFPA-30. |
| | PLEASE PROVIDE LAYOUT FOR DISTANES OF DISCONNECTING |
| | MEANS FOR PUMPS ETC. |
| | |
| | 3) NOTE: PLEASE SHOW A DETAIL FOR THE DISCONNECTING |
| | MEANS. A MUSHROOM BUTTON |
| | IS SHOWN, HOWEVER NO INFORMATION/DETAIL |
| | IS SHOWN ON HOW THIS WILL BE TIED INTO |
| | THE BRANCH CIRCUITS REQUIRED TO BE SHUT |
| | DOWN. |
| | 514.11 |
| | PLEASE SEE 514 IN HAND BOOK AS EXAMPLES |
| | ARE SHOWN. |
| | |
| | 4) NOTE: PLEASE CORRELATE SERVICES, |
| | PANELS ON RISER DIAGRAM. |
| | PLEASE SEE SERVICE IS SHOWN W/ 1-PHASE DISCONNECTS, YET |
| | PANEL SHOWN AS 3-PHASE? |
| | PLEASE SEE FEEDERS SHOWN AS 1-PHASE AND |
| | 3-PHASE ON THE LINE SIDE OF SERVICE |
| | MAINS?? |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE CORRLEATE PANEL SIZES, |
| | CIRCUITING ETC. |
| | 24 CIR 225A ?? PLEASE VERIFY AS 225A |
| | PANELS ARE NOT COMMON FOR 24 CIRCUITS? |
| | PLEASE SEE PANELS SHOWN AS 30 CIRCUIT, |
| | YET RISER SHOWS THESE AS 42 CIRCUIT? |
| | |
| | 6) NOTE: PLEASE SEE PANEL "A" SHOWN AS |
| | 200I)?? |
| | PLEASE CLARIFY THIS. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE RISER SHOWS THE GEC |
| | GOING TO THE FOUNDATION STEEL. PLEASE |
| | KNOW, THIS IS PERMITTED, HOWEVER NOT |
| | REQUIRED ON AN EXISTING BUILDING. |
| | PLEASE KNOW, THE STRUCTURAL INTEGRITY OF |
| | THIS FOOTER MAY BE AFFECT DUE TO THE AGE |
| | OF THE EXISTING BUILDING. |
| | 250.50 THIS MAY BE DONE, AS IF THIS IS |
| | SHOWN ON PLANS, THEN THIS ATTACHMENT |
| | WILL BE REQUIRED. |
| | |
| | 8) NOTE: PLEASE SEE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" IS BEING SHOWN |
| | BEFORE THE FIRST MEANS OF DISCONNECT FOR |
| | THE SERVICE. PLEASE SEE 250.6, 250.24B, |
| | AS THIS IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 9) NOTE: PLEASE INDICATE THE SIZE OF THE |
| | EXISITNG OR NEW SEC'S ON RISER. |
| | 215.5 |
| | CAN NOT VERIFY AT THIS TIME. |
| | |
| | 10) NOTE: PLEASE SEE SOME PANELS ARE |
| | SHOWN AS 120/240V AND OTHERS AS |
| | 120/208V? |
| | PLEASE CORRELATE AND ADJUST ALL LOAD |
| | CALCS. |
| | 215.5 |
| | |
| | 11) NOTE: PLEASE SEE CALCS ARE SHOWN FOR |
| | 3-PHASE, HOWEVER THIS IS NOT CLEAR AS |
| | SERVICE IS ALSO SHOWN AS 1-PHASE?? |
| | |
| | 12) NOTE: PLEASE SEE 210.8B3 IN KITCHEN |
| | AREAS IN OTHER THAN DWELLING UNITS. |
| | |
| | 13) NOTE: PLEASE SEE ANY OUTSIDE RECEPTS |
| | FO ICE ETC SHALL BE GFI. ONLY NOTED. |
| | |
| | 14) NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS PER FAC |
| | 61G15-23.002, FS 471.023. |
| | MISSING CERTIFICATE OF AUTHORIZATION #. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | ** PLEASE KNOW, AS PLANS ARE NOT |
| | COMPLETE AT THIS TIME, A FULL REVIEW FOR |
| | CODE COMPLIANCE CAN NOT BE DONE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |