Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-16 00:00:00******* UNSAT ********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE VALUATION FOR COMPLETE
 SCOPE OF SHALL BE ADJUSTED FOR ALL LABOR
 AND MATERIALS, EVEN IF ANY MATERIALS ARE
 OWNER SUPPLIED. FBC 108.3.
 VALUE SHOWN SEEMS LOW FOR SCOPE OF WORK
 SHOWN ON PLANS.
 PLEASE ADJUST.
  
 1) NOTE: PLEASE SEE ALL CURRENT CODES
 ADOPTED BY THE STATE SHALL BE REFERENCE
 ON PLANS. 2002, NFPA-70, 2004 FBC ETC.
 PLEASE ALSO SEE ALL CURRENT CODES.
 PLEASE ALSO SEE PLANS INDICATE "PALM
 BEACH COUNTY BUILDING DEPARTMENT".
 PLEASE KNOW, THIS SCOPE OF WORK IS DONE
 IN THE "CITY OF WEST PALM BEACH".
  
 2) NOTE: PLEASE CLEARLY LABEL AND
 IDENTIFY ALL CLASS/DIVISION LOCATIONS
 PER NEC 514, NFPA-30.
 PLEASE PROVIDE LAYOUT FOR DISTANES OF DISCONNECTING
 MEANS FOR PUMPS ETC.
  
 3) NOTE: PLEASE SHOW A DETAIL FOR THE DISCONNECTING
 MEANS. A MUSHROOM BUTTON
 IS SHOWN, HOWEVER NO INFORMATION/DETAIL
 IS SHOWN ON HOW THIS WILL BE TIED INTO
 THE BRANCH CIRCUITS REQUIRED TO BE SHUT
 DOWN.
 514.11
 PLEASE SEE 514 IN HAND BOOK AS EXAMPLES
 ARE SHOWN.
  
 4) NOTE: PLEASE CORRELATE SERVICES,
 PANELS ON RISER DIAGRAM.
 PLEASE SEE SERVICE IS SHOWN W/ 1-PHASE DISCONNECTS, YET
 PANEL SHOWN AS 3-PHASE?
 PLEASE SEE FEEDERS SHOWN AS 1-PHASE AND
 3-PHASE ON THE LINE SIDE OF SERVICE
 MAINS??
 215.5
  
 5) NOTE: PLEASE CORRLEATE PANEL SIZES,
 CIRCUITING ETC.
 24 CIR 225A ?? PLEASE VERIFY AS 225A
 PANELS ARE NOT COMMON FOR 24 CIRCUITS?
 PLEASE SEE PANELS SHOWN AS 30 CIRCUIT,
 YET RISER SHOWS THESE AS 42 CIRCUIT?
  
 6) NOTE: PLEASE SEE PANEL "A" SHOWN AS
 200I)??
 PLEASE CLARIFY THIS.
 215.5
  
 7) NOTE: PLEASE SEE RISER SHOWS THE GEC
 GOING TO THE FOUNDATION STEEL. PLEASE
 KNOW, THIS IS PERMITTED, HOWEVER NOT
 REQUIRED ON AN EXISTING BUILDING.
 PLEASE KNOW, THE STRUCTURAL INTEGRITY OF
 THIS FOOTER MAY BE AFFECT DUE TO THE AGE
 OF THE EXISTING BUILDING.
 250.50 THIS MAY BE DONE, AS IF THIS IS
 SHOWN ON PLANS, THEN THIS ATTACHMENT
 WILL BE REQUIRED.
  
 8) NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT FOR
 THE SERVICE. PLEASE SEE 250.6, 250.24B,
 AS THIS IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE INDICATE THE SIZE OF THE
 EXISITNG OR NEW SEC'S ON RISER.
 215.5
 CAN NOT VERIFY AT THIS TIME.
  
 10) NOTE: PLEASE SEE SOME PANELS ARE
 SHOWN AS 120/240V AND OTHERS AS
 120/208V?
 PLEASE CORRELATE AND ADJUST ALL LOAD
 CALCS.
 215.5
  
 11) NOTE: PLEASE SEE CALCS ARE SHOWN FOR
 3-PHASE, HOWEVER THIS IS NOT CLEAR AS
 SERVICE IS ALSO SHOWN AS 1-PHASE??
  
 12) NOTE: PLEASE SEE 210.8B3 IN KITCHEN
 AREAS IN OTHER THAN DWELLING UNITS.
  
 13) NOTE: PLEASE SEE ANY OUTSIDE RECEPTS
 FO ICE ETC SHALL BE GFI. ONLY NOTED.
  
 14) NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS PER FAC
 61G15-23.002, FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION #.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PLEASE KNOW, AS PLANS ARE NOT
 COMPLETE AT THIS TIME, A FULL REVIEW FOR
 CODE COMPLIANCE CAN NOT BE DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]