Notes
Date Text
2006-05-17 00:00:00****CORRECTIONS****
 ****PLAN CHECK ONLY, NOT A PERMIT
 APPLICATION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.)DECLARE OCCUPANCY FBC309, MINIMUM
 BUILDING TYPE FBC6.
  
 5.)DECLARE AN OCCUPANT LOAD, FBC10.
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR ENG, INC. IS TO BE ON EACH
 SHEET, FAC61G15-23.002.
  
 7.)PRODUCT APPROVALS REQUIRED FOR THE
 STOREFRONT AND DOORS.FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72. WWW.FLORIDABUILDING.ORG
  
 8.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 9.)A-1B HAS A NOTE REFERRING TO
 HURRICANE SHUTTERS.USE OF REMOVABLE
 SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.SEE
 ATTACHED MISSILE IMPACT PROTECTION
 STANDARD, ITEM 13.THE PLANS WILL NOT
 BE APPROVED WITH THIS REFERENCE TO
 HURRICANE SHUTTERS UNLESS THE
 INSTALLATION PLAN REFERRED TO IN THE
 STANDARD IS APPROVED.THE PLAN MAY BE
 SUBMITTED SEPARATELY AND PRIOR TO
 RESUBMITTAL OF THE CONSTRUCTION PERMIT
 PLANS.
  
 10.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 11.)EXIT ACCESS SHALL NOT GO THROUGH
 STORAGE ROOMS, FBC1013.2.
  
 12.)THE BOTTOM OF EACH RAMP SHALL HAVE
 72IN STRAIGHT AND LEVEL CLEARANCE,
 FBC11-4.8.4(2).
  
 13.)PARKING IS NOT SHOWN ON THE PLAN.
 IF PARKING IS PROVIDED, ACCESSIBLE
 PARKING IS REQUIRED FBC11-4.6.SEE
 ATTACHED DETAIL.
  
 14.)SEE 11-7.2, SHOW COMPLIANCE FOR
 THE SALES COUNTER AT THE POS.THE
 HEIGHT IS SHOWN GRAPHICALLY A-A4 BUT
 PLEASE ADD THE DIMENSION TO THE COUNTER
 WHICH HAS A HEIGHT REQUIREMENT (SALES
 AREA SIDE).
  
 15.)PLANS INDICATE THAT THE EXISTING
 MANSARD IS TO BE RESURFACED A3.ROOF
 PERMIT REQUIRED.
  
 16.)PROVIDE A BREAKDOWN OF COSTS TO
 DETERMINE WHETHER OR NOT ENERGY CALCS
 ARE REQUIRED AND TO CONFIRM VALUATION
 PROVIDED.SEE FBC 13-101.1, FBC13-202,
 FBC EB708.1.
  
 17.)IF ENERGY CALCS ARE REQUIRED,
 PLEASE PROVIDE AND SIGN IN ALL
 APPLICABLE PLACES, INCLUDING THE
 OWNER/AGENT LINE FBC13-103.1.
  
 18.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC TABLE 803.5.
  
 19.)THERE IS A NOTE ON M2 STATING THAT
 EQUIPMENT IS TO BE ANCHORED PER FBC 15
 AND 16 AND TO WITHSTAND 146MPH.SPECIFY
 ANCHORING.
  
 20.)THE TABLE ON M2 IS FROM HIGH
 VELOCITY, NOT COMPLIANT FOR NON HIGH
 VELOCITY.THE EQUIPMENT CLEARANCE IS TO
 COMPLY WITH FBC1509.7.
  