| Plan Review Notes For Permit 06040937 |
| Permit Number |
06040937 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-30 00:00:00 | *** PROVISO *** | | | 1)BALANCED RETURN AIR. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. PER 2004 | | | FBC/R M1602.4 . | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|