| 2006-05-17 00:00:00 | ****** UNSAT ******* |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS DONE BY A |
| | MIN OF AN ARCHITECT PER FS 481.229 FOR |
| | VALUE AND SCOPE OF WORK OVER $25,000. |
| | |
| | 2) NOTE: PLEASE PROVIDE THE RISER |
| | DIAGRAM, AS PLANS SEEM TO SHOW TWO |
| | DIFFERENT METERS ??. THIS IS BEING SHOWN |
| | AS A SINGLE OCCUPANCY BUILDING AND NO |
| | "FIRE WALL" SEPARATION IS PRESENT ON |
| | PLANS. PLEASE KNOW, ONLY ONE SERVICE |
| | WILL BE PERMITTED AND ALL MAINS SHALL BE |
| | GROUPED. 230.2,230.70,230.72 |
| | |
| | 3) NOTE: PLEASE SEE 517 AND INDICATE |
| | LOCATIONS AND WIRING METHODS AS SET |
| | FORTH IN THE 2002 NEC AND LS CODE. |
| | PLEASE SEE ALL OTHER COMMENTS FROM OTHER |
| | TRADES WHICH MAY ALSO AFFECT THIS. |
| | |
| | 4)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF ALL EM/EXT LTS. |
| | |
| | 5) NOTE: PLEASE SEE THE MIN OCP AND AWG |
| | FOR EXISTING AHU'S SHALL BE ADJUSTED |
| | EVEN IF EXISITNG. PLEASE SEE |
| | 424.3B,240.4,310.16 10KW, #8 AND 50A |
| | OCP. |
| | |
| | 6) NOTE: PLEASE SUPPLY LOAD CALCUALTIONS |
| | PER 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE SEE 215.3,230.42 FOR ALL |
| | CONTINUOUS LOADS TO BE SHOWN AT 125%. |
| | |
| | 7) NOTE: PLANS SHALL CONTAIN THE CURRENT |
| | CODES UNDER ADOPTION BY THE STATE OF |
| | FLORIDA. |
| | 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72 ETC. |
| | |
| | 8) NOTE: PLEASE SEE BUIDLIGN REVIEW |
| | COMMENTS FOR REQUIRED "STATEMENT" ON |
| | PLANS FOR THE DESIGN PROFESSIONAL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |