| Plan Review Notes For Permit 06040933 |
| Permit Number |
06040933 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-12 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THERE ARE TWO RISERS ON SHEET #5, | | | REMOVE THE ONE NOT BEING USED. | | | | | | 2} THE "SUB -PANEL" SHOWN ON BOTH RISERS | | | MUST BE GROUNDED PER 250.32, AN DHAV EA | | | DISCONNECTING MEANS PER 225.31. | | | | | | 3} THERE IS A METER SHOWN ON THE POOL | | | HOUSE, PLEASE VERIFY, ADD TO RISER. | | | | | | 4} LOCATE THE SUB PANEL AT THE POOLHOUSE | | | ON THE PLAN. | | | | | | 5} THE "NEW BATH" SHOWN ON THE PLAN MUST | | | COMPLY WITH 210.11(C)(3). | | | | | | 6} PROVIDE A PANEL SCHEDULE FOR THE POOL | | | SUB PANEL. | | | | | | 7} SEE 106.1 FBC. THE PERSON TAKING | | | RESPONSIBILITY FOR THE PLAN MUST PRINT | | | AND SIGN NAME ON SAME. | | | | | | 8} PLEASE SEE ARTICLE 108.3 FBC AS | | | AMMENDED FOR VALUATION OF THE PROJECT, | | | INCREASE VALUE AT THE FRONT COUNTER | | | PRIOR TO RESUBMITTING. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|