| Date |
Text |
| 2006-08-06 00:00:00 | ******* UNSAT 2ND REVIEW ****** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED AS THE |
| | SAME ELECTRICAL RISER DIAGRAM WAS |
| | SUBMITTED BACK FOR REVIEW. |
| | PLEASE ALSO NEW COMMENTS DUE TO |
| | PLANS/DESIGNS ETC SUBMITTED. |
| | PLEASE SEE COMMENT BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | * NEW NOTE ARE ADDED AT BOTTOM. |
| | |
| | 1)NOTE:OK, HOWEVER PLEASE SEE BLDG |
| | REVIEW COMMEWNTS ALSO AS THE SLAB DETAIL |
| | PAPERWORK NOW CONTAINS A SEL BY THE |
| | ENEGINEER WHICH IS NO LONGER VALID AND |
| | CAN NOT BE USED. PLEASE SEE RULING BY |
| | THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS IN FEB 04 WHICH RULE |
| | 61G15-23.001 CHANGED AND ENGINEER'S MUST |
| | OBTIAN NEW SEALS BY DEC 31ST, 2005. |
| | PLEASE KNOW THE SEAL WITH THE WORDING OF |
| | "CERTIFICATE" IS NOT ACCEPTABLE AND MUST |
| | CONTAIN THE WORDING OF "LICENSE". |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE BLDG REVIEW COMMENTS |
| | AS DETAIL FOR SLAB.MUST CONTAIN A |
| | PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLAN. |
| | |
| | 2)NOTE:NO, THIS WAS NOT DONE. THE SAME |
| | PLANS WERE SUBMITTED BACK. |
| | ** PLEASE KNOW GENERATOR IS BEING SHOWN |
| | UP AGAINST BUILDING. IT IS KNOWN TO THIS |
| | OFFICE THIS GENERATOR FROM GENERAC |
| | REQUIRES 5'FT MIN FROM ALL SURROUNDING |
| | BLDG/WALLS. |
| | 110.3,90.8 |
| | IF DISTANCE IS LESS, MUST CONTAIN |
| | SPECIFIC MIN CLEARENCES FROM |
| | MANUFACTURE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE AN OVERVIEW/LAYOUT OF ALL |
| | EQUIPMENT AND WHERE THIS IS LOCATED AT |
| | SITE. PLEASE KNOW THIS IS NEED FOR |
| | VERIFICATION FOR MEANS OF DISCONNECT. |
| | PLEASE ALSO SEE ZONING COMMENTS AS A |
| | SITE PLAN WAS NOT SUBMITTED INDICATIING |
| | ALL SETBACKS. |
| | |
| | 3)NOTE: NO, SAME PLANS SUBMITTED BACK. |
| | NO DISOCNNECTING MEANS IS SHOWN FOR |
| | FEEDERS EITHER FROM GEN TO THE ATS |
| | GROUPED WITH EXISTING MAIN OR DISCONNECT |
| | ON THE LOAD SIDE OF THE ATS GROUPED WIHT |
| | EXISTING MAINS. |
| | PLEASE KNOW, IF THERE IS A SERVICE MAIN |
| | DISCONNETC ON THE LINE SIDE OF TEH ATS, |
| | THIS ATS IS NOT REQUIRED TO BE "SERVICE |
| | ENTRANCE" RATED, ONLY RATED AS "SERVICE |
| | EQUIPMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY IF THE EXISTING |
| | PANEL (#8) IS LOCATED WITH OTHER MAINS? |
| | PLEASE KNOW, A MEANS OF DISCONNECT WILL |
| | BE REQUIRED EITHER ON THE LINE SIDE OF |
| | ATS FROM GEN OR THE LOAD SIDE OF THE |
| | ATS. THIS DISCONNECT WILL NOT REQUIRED |
| | OCP, ONLY A DISCONNECTING MENS FOR THE |
| | LOAD SERVED. |
| | PLEASE ALSO KNOW, SPECS SUBMITTED |
| | INDICATE A SERVICE ENTRANCE RATED ATS??? |
| | PLEASE KNOW, SINCE A MAIN IS SHOWN ON |
| | THE LINE SIDE OF ATS , A SE RATED ATS IS |
| | NOT REQUIRED. THIS ATS AS SHOWN ONLY |
| | DISCONNECTS THE FEED COMING FROM THE |
| | NORMAL POWER SIDE. |
| | PLEASE SEE 225.31-225.39. |
| | |
| | |
| | 4)NOTE: OK, VALUE WAS INCREASED ON NEW |
| | CONTRACTORS APPLICATION, HOWEVER THE |
| | ADDITIONALS FEES WERE NOT PAID FOR WHEN |
| | PLANS WERE RESUBMITTED. OWES $425.65 |
| | MUST BE PAID BEFORE PERMIT CAN BE |
| | ISSUED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** PLEASE SEE |
| | VALUATION IS BASED ON |
| | COMPLETE SCOPE PF WORK WHICH IS TO |
| | INCLUDE ALL LABOUR AND MATERIALS, EVEN |
| | OF ANY EQUIPMENT IS OWNER SUPPLIED. |
| | VALUE AS SHOWN IS WAY LOW AND MAY BE |
| | ADJUSTED BY THIS OFFICE IF AN |
| | APPROPRIATE VALUE IS NOT INCREASED. |
| | THIS IS TO BE INCREASED WHEN |
| | RESUBMITTING PLANS AFTER ALL REVIEWS ARE |
| | COMPLETED. |
| | PLEASE SEE THE VALUE OF $2K MUST REFLECT |
| | ALL SCOPE. FBC 108.3 |
| | |
| | 5)NOTE: OK, HOWEVER PLEASE STATE |
| | OCCUPANCY |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE INTENDED LOADS |
| | FOR GENERATOR. GEN MUST BE SIZED FOR |
| | LOADS SERVED. PLEASE SEE LOAD SUMMARY |
| | PROVIDED THIS DOES NOT SEEM TO ADD UP? |
| | PLEASE VERIFY LOADS AS SHOWN FOR UNIT. |
| | PLEASE KNOW THE UNTI MUST BE SIZED FOR |
| | THE LOADS SERVED OR PLEASE DETAIL |
| | "AUTOMATIC LOAD SHEEDING METHOD BEING |
| | USED. |
| | 220, 215.5, 702.5 |
| | |
| | |
| | 6) NOTE: NO, THIS IS REQUIRED FOR ALL |
| | SHEETS INCLUDING RISER DIAGRAM ETC WHICH |
| | IS TO B REVISED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT ALL PLANS AND |
| | SHEETS CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | SAID PLANS AND DRAWINGS. |
| | 104.2.1, 106.1.2 FBC |
| | |
| | ** NEW NOTE ** |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)B) WITH |
| | REPSECT THE DESIGN PROFESSIONAL AND |
| | REPEAT CODE COMPLIANT COMMENTS. |
| | THIS IS ONLY BEING GIVEN AS A NOTE AT |
| | THIS TIME. |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |