Plan Review Notes
Plan Review Notes For Permit 06040879
Permit Number 06040879
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-06 00:00:00******* UNSAT 2ND REVIEW ******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED AS THE
 SAME ELECTRICAL RISER DIAGRAM WAS
 SUBMITTED BACK FOR REVIEW.
 PLEASE ALSO NEW COMMENTS DUE TO
 PLANS/DESIGNS ETC SUBMITTED.
 PLEASE SEE COMMENT BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
 * NEW NOTE ARE ADDED AT BOTTOM.
  
 1)NOTE:OK, HOWEVER PLEASE SEE BLDG
 REVIEW COMMEWNTS ALSO AS THE SLAB DETAIL
 PAPERWORK NOW CONTAINS A SEL BY THE
 ENEGINEER WHICH IS NO LONGER VALID AND
 CAN NOT BE USED. PLEASE SEE RULING BY
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS IN FEB 04 WHICH RULE
 61G15-23.001 CHANGED AND ENGINEER'S MUST
 OBTIAN NEW SEALS BY DEC 31ST, 2005.
 PLEASE KNOW THE SEAL WITH THE WORDING OF
 "CERTIFICATE" IS NOT ACCEPTABLE AND MUST
 CONTAIN THE WORDING OF "LICENSE".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE BLDG REVIEW COMMENTS
 AS DETAIL FOR SLAB.MUST CONTAIN A
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLAN.
  
 2)NOTE:NO, THIS WAS NOT DONE. THE SAME
 PLANS WERE SUBMITTED BACK.
 ** PLEASE KNOW GENERATOR IS BEING SHOWN
 UP AGAINST BUILDING. IT IS KNOWN TO THIS
 OFFICE THIS GENERATOR FROM GENERAC
 REQUIRES 5'FT MIN FROM ALL SURROUNDING
 BLDG/WALLS.
 110.3,90.8
 IF DISTANCE IS LESS, MUST CONTAIN
 SPECIFIC MIN CLEARENCES FROM
 MANUFACTURE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE AN OVERVIEW/LAYOUT OF ALL
 EQUIPMENT AND WHERE THIS IS LOCATED AT
 SITE. PLEASE KNOW THIS IS NEED FOR
 VERIFICATION FOR MEANS OF DISCONNECT.
 PLEASE ALSO SEE ZONING COMMENTS AS A
 SITE PLAN WAS NOT SUBMITTED INDICATIING
 ALL SETBACKS.
  
 3)NOTE: NO, SAME PLANS SUBMITTED BACK.
 NO DISOCNNECTING MEANS IS SHOWN FOR
 FEEDERS EITHER FROM GEN TO THE ATS
 GROUPED WITH EXISTING MAIN OR DISCONNECT
 ON THE LOAD SIDE OF THE ATS GROUPED WIHT
 EXISTING MAINS.
 PLEASE KNOW, IF THERE IS A SERVICE MAIN
 DISCONNETC ON THE LINE SIDE OF TEH ATS,
 THIS ATS IS NOT REQUIRED TO BE "SERVICE
 ENTRANCE" RATED, ONLY RATED AS "SERVICE
 EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY IF THE EXISTING
 PANEL (#8) IS LOCATED WITH OTHER MAINS?
 PLEASE KNOW, A MEANS OF DISCONNECT WILL
 BE REQUIRED EITHER ON THE LINE SIDE OF
 ATS FROM GEN OR THE LOAD SIDE OF THE
 ATS. THIS DISCONNECT WILL NOT REQUIRED
 OCP, ONLY A DISCONNECTING MENS FOR THE
 LOAD SERVED.
 PLEASE ALSO KNOW, SPECS SUBMITTED
 INDICATE A SERVICE ENTRANCE RATED ATS???
 PLEASE KNOW, SINCE A MAIN IS SHOWN ON
 THE LINE SIDE OF ATS , A SE RATED ATS IS
 NOT REQUIRED. THIS ATS AS SHOWN ONLY
 DISCONNECTS THE FEED COMING FROM THE
 NORMAL POWER SIDE.
 PLEASE SEE 225.31-225.39.
  
  
 4)NOTE: OK, VALUE WAS INCREASED ON NEW
 CONTRACTORS APPLICATION, HOWEVER THE
 ADDITIONALS FEES WERE NOT PAID FOR WHEN
 PLANS WERE RESUBMITTED. OWES $425.65
 MUST BE PAID BEFORE PERMIT CAN BE
 ISSUED.
  
 ** PREVIOUS REVIEW NOTE ** PLEASE SEE
 VALUATION IS BASED ON
 COMPLETE SCOPE PF WORK WHICH IS TO
 INCLUDE ALL LABOUR AND MATERIALS, EVEN
 OF ANY EQUIPMENT IS OWNER SUPPLIED.
 VALUE AS SHOWN IS WAY LOW AND MAY BE
 ADJUSTED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INCREASED.
 THIS IS TO BE INCREASED WHEN
 RESUBMITTING PLANS AFTER ALL REVIEWS ARE
 COMPLETED.
 PLEASE SEE THE VALUE OF $2K MUST REFLECT
 ALL SCOPE. FBC 108.3
  
 5)NOTE: OK, HOWEVER PLEASE STATE
 OCCUPANCY
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE INTENDED LOADS
 FOR GENERATOR. GEN MUST BE SIZED FOR
 LOADS SERVED. PLEASE SEE LOAD SUMMARY
 PROVIDED THIS DOES NOT SEEM TO ADD UP?
 PLEASE VERIFY LOADS AS SHOWN FOR UNIT.
 PLEASE KNOW THE UNTI MUST BE SIZED FOR
 THE LOADS SERVED OR PLEASE DETAIL
 "AUTOMATIC LOAD SHEEDING METHOD BEING
 USED.
 220, 215.5, 702.5
  
  
 6) NOTE: NO, THIS IS REQUIRED FOR ALL
 SHEETS INCLUDING RISER DIAGRAM ETC WHICH
 IS TO B REVISED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ALL PLANS AND
 SHEETS CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 SAID PLANS AND DRAWINGS.
 104.2.1, 106.1.2 FBC
  
 ** NEW NOTE **
  
 7) NOTE: PLEASE SEE FS 553.80(2)B) WITH
 REPSECT THE DESIGN PROFESSIONAL AND
 REPEAT CODE COMPLIANT COMMENTS.
 THIS IS ONLY BEING GIVEN AS A NOTE AT
 THIS TIME.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW