| 2006-05-09 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | AS DETAIL FOR SLAB.MUST CONTAIN A |
| | PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLAN. |
| | |
| | 2)NOTE: PLEASE PROVIDE AN |
| | OVERVIEW/LAYOUT OF ALL EQUIPMENT AND |
| | WHERE THIS IS LOCATED AT SITE. PLEASE |
| | KNOW THIS IS NEED FOR VERIFICATION FOR |
| | MEANS OF DISCONNECT. |
| | PLEASE ALSO SEE ZONING COMMENTS AS A |
| | SITE PLAN WAS NOT SUBMITTED INDICATIING |
| | ALL SETBACKS. |
| | |
| | 3)NOTE: PLEASE CLAROFY IF THE EXISTING |
| | PANEL (#8) IS LOCATED WITH OTHER MAINS? |
| | PLEASE KNOW, A MEANS OF DISCONNECT WILL |
| | BE REQUIRED EITHER ON THE LINE SIDE OF |
| | ATS FROM GEN OR THE LOAD SIDE OF THE |
| | ATS. THIS DISCONNECT WILL NOT REQUIRED |
| | OCP, ONLY A DISCONNECTING MENS FOR THE |
| | LOAD SERVED. |
| | PLEASE ALSO KNOW, SPECS SUBMITTED |
| | INDICATE A SERVICE ENTRANCE RATED ATS??? |
| | PLEASE KNOW, SINCE A MAIN IS SHOWN ON |
| | THE LINE SIDE OF ATS , A SE RATED ATS IS |
| | NOT REQUIRED. THIS ATS AS SHOWN ONLY |
| | DISCONNECTS THE FEED COMING FROM THE |
| | NORMAL POWER SIDE. |
| | PLEASE SEE 225.31-225.39. |
| | |
| | |
| | 4)NOTE: PLEASE SEE VALUATION IS BASED ON |
| | COMPLETE SCOPE PF WORK WHICH IS TO |
| | INCLUDE ALL LABOUR AND MATERIALS, EVEN |
| | OF ANY EQUIPMENT IS OWNER SUPPLIED. |
| | VALUE AS SHOWN IS WAY LOW AND MAY BE |
| | ADJUSTED BY THIS OFFICE IF AN |
| | APPROPRIATE VALUE IS NOT INCREASED. |
| | THIS IS TO BE INCREASED WHEN |
| | RESUBMITTING PLANS AFTER ALL REVIEWS ARE |
| | COMPLETED. |
| | PLEASE SEE THE VALUE OF $2K MUST REFLECT |
| | ALL SCOPE. |
| | |
| | 5)NOTE: PLEASE SUBMIT THE INTENDED LOADS |
| | FOR GENERATOR. GEN MUST BE SIZED FOR |
| | LOADS SERVED. PLEASE SEE LOAD SUMMARY |
| | PROVIDED THIS DOES NOT SEEM TO ADD UP? |
| | PLEASE VERIFY LOADS AS SHOWN FOR UNIT. |
| | PLEASE KNOW THE UNTI MUST BE SIZED FOR |
| | THE LOADS SERVED OR PLEASE DETAIL |
| | "AUTOMATIC LOAD SHEEDING METHOD BEING |
| | USED. |
| | 220, 215.5, 702.5 |
| | |
| | *** |
| | 6) NOTE: PLEASE SEE THAT ALL PLANS AND |
| | SHEETS CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | SAID PLANS AND DRAWINGS. |
| | 104.2.1 |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |