Plan Review Notes
Plan Review Notes For Permit 06040879
Permit Number 06040879
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-09 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS DETAIL FOR SLAB.MUST CONTAIN A
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLAN.
  
 2)NOTE: PLEASE PROVIDE AN
 OVERVIEW/LAYOUT OF ALL EQUIPMENT AND
 WHERE THIS IS LOCATED AT SITE. PLEASE
 KNOW THIS IS NEED FOR VERIFICATION FOR
 MEANS OF DISCONNECT.
 PLEASE ALSO SEE ZONING COMMENTS AS A
 SITE PLAN WAS NOT SUBMITTED INDICATIING
 ALL SETBACKS.
  
 3)NOTE: PLEASE CLAROFY IF THE EXISTING
 PANEL (#8) IS LOCATED WITH OTHER MAINS?
 PLEASE KNOW, A MEANS OF DISCONNECT WILL
 BE REQUIRED EITHER ON THE LINE SIDE OF
 ATS FROM GEN OR THE LOAD SIDE OF THE
 ATS. THIS DISCONNECT WILL NOT REQUIRED
 OCP, ONLY A DISCONNECTING MENS FOR THE
 LOAD SERVED.
 PLEASE ALSO KNOW, SPECS SUBMITTED
 INDICATE A SERVICE ENTRANCE RATED ATS???
 PLEASE KNOW, SINCE A MAIN IS SHOWN ON
 THE LINE SIDE OF ATS , A SE RATED ATS IS
 NOT REQUIRED. THIS ATS AS SHOWN ONLY
 DISCONNECTS THE FEED COMING FROM THE
 NORMAL POWER SIDE.
 PLEASE SEE 225.31-225.39.
  
  
 4)NOTE: PLEASE SEE VALUATION IS BASED ON
 COMPLETE SCOPE PF WORK WHICH IS TO
 INCLUDE ALL LABOUR AND MATERIALS, EVEN
 OF ANY EQUIPMENT IS OWNER SUPPLIED.
 VALUE AS SHOWN IS WAY LOW AND MAY BE
 ADJUSTED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INCREASED.
 THIS IS TO BE INCREASED WHEN
 RESUBMITTING PLANS AFTER ALL REVIEWS ARE
 COMPLETED.
 PLEASE SEE THE VALUE OF $2K MUST REFLECT
 ALL SCOPE.
  
 5)NOTE: PLEASE SUBMIT THE INTENDED LOADS
 FOR GENERATOR. GEN MUST BE SIZED FOR
 LOADS SERVED. PLEASE SEE LOAD SUMMARY
 PROVIDED THIS DOES NOT SEEM TO ADD UP?
 PLEASE VERIFY LOADS AS SHOWN FOR UNIT.
 PLEASE KNOW THE UNTI MUST BE SIZED FOR
 THE LOADS SERVED OR PLEASE DETAIL
 "AUTOMATIC LOAD SHEEDING METHOD BEING
 USED.
 220, 215.5, 702.5
  
 ***
 6) NOTE: PLEASE SEE THAT ALL PLANS AND
 SHEETS CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 SAID PLANS AND DRAWINGS.
 104.2.1
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]