Plan Review Notes
Plan Review Notes For Permit 06040875
Permit Number 06040875
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-03 00:00:00 
  
 THE GENERATOR OUTPUT IS NOT ADEQUATE FOR
 THE LOAD SERVED, 702.5. THE GENERATOR
 OUTPUT IS 112 AMPS PER SPEC, AND THE
 LOAD IN PANEL "A" CALCULATED @ 160 AMPS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW