| Plan Review Notes For Permit 06040875 |
| Permit Number |
06040875 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-03 00:00:00 | | | | | | | THE GENERATOR OUTPUT IS NOT ADEQUATE FOR | | | THE LOAD SERVED, 702.5. THE GENERATOR | | | OUTPUT IS 112 AMPS PER SPEC, AND THE | | | LOAD IN PANEL "A" CALCULATED @ 160 AMPS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|