| 2006-05-02 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 PLUMBING | | | | | | PLEASE ADJUST YOUR DRAWINGS TO REFLECT | | | THE FOLLOWING CHANGES REQUIRED FOR PLAN | | | REVIEW: NOTE, ONLY ONE DRAWING INDICATES | | | PLUMBING CORRECTIONS: | | | | | | 1. THE SHOWER INDICATED ON THE ISOMETRIC | | | DRAINAGE RISER DIAGRAM ON SHEET A-3 IS | | | NOT VENTED PER 909.1 WET VENTS, PLEASE | | | SEE CORRECTED DRAWING AND ADJUST | | | DRAWINGS FOR RESUBMITTAL. | | | 2. THE WASHING MACHINE INDICATED ON THE | | | ISOMETRIC DRAINAGE RISER DIAGRAM IS NOT | | | SIZED PER 406.3, BRANCH DRAIN OR | | | DRAINAGE STACK MINIMUM 3". PER 708.7 | | | CLEANOUTS SHALL BE THE SAME NOMINAL SIZE | | | AS THE PIPE THEY SERVE UP TO 4". PER | | | 708.9 ACCESS SHALL BE PROVIDED TO ALL | | | CLEANOUTS. PLEASE SEE CORRECTED DRAWING | | | AND ADJUST DRAWINGS FOR RESUBMITTAL. | | | 3. PLEASE INDICATE THE WASHING MACHINE, | | | DRYER, AND WATER HEATER ON THE PROPOSED | | | FLOOR PLAN. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K/STEVENS | | | (561) 805-6721 |
|