| 2006-06-13 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING IS STILL REQUIRED FOR |
| | PLUMBING PLAN REVIEW: |
| | |
| | 1.THERE HAS BEEN NO ATTEMPT TO CORRECT |
| | THE ISOMETRIC PLUMBING RISER DIAGRAM ON |
| | SHEET 3/3, UNTIL THESE CHANGES HAVE BEEN |
| | MET PERMIT CAN NOT BE ISSUED. |
| | 2. CHANGE UNDER SINK VENT TO READ AIR |
| | ADMITTANCE VALVE PER FBC-2004 PLUMBING |
| | SECTION 917, SEE CORRECTED DRAWING ON |
| | SHEET 3/3 IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | 3. PER CHAPTER 1, SECTION 106.1.1: THE |
| | SANITARY ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. SHEET 3/3 |
| | FLOOR PLAN INDICATES TWO 2" PVC UNDER |
| | SINK VENTS WHICH SHOULD BE INDICATED AS |
| | AIR ADMITTANCE VALVES (A.A.V.) AND RISER |
| | DIAGRAM INDICATES ONE AIR ADMITTANCE |
| | VALVE (A.A.V.) PLEASE CORRELATE DRAWING |
| | FOR RESUBMITTAL. |
| | 4.CLEANOUTS ARE REQUIRED AT THE BASE OF |
| | WASTE STACKS AND NEAR THE JUNCTION OF |
| | THE BUILDING DRAIN AND THE BUILDING |
| | SEWER, PER FBC-2004 PLUMBING, SECTION |
| | 708.3.4 AND SECTION 708.3.5. THE |
| | ISOMETRIC PLUMBING RISER DIAGRAM NEEDS |
| | TO INDICATE THE CLEANOUTS, PLEASE SEE |
| | CORRECTED DRAWING IN RED INK FOR |
| | REFERENCE FOR RESUBMITTAL. |
| | 5.NOTE: A PLUMBING PERMIT WILL BE |
| | REQUIRED FOR THE PLUMBING WORK INDICATED |
| | ON DRAWINGS, PLUMBING CONTRACTOR SHALL |
| | REFERENCE PERMIT #06040807 WHEN PLUMBING |
| | PERMIT IS APPLIED FOR. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | |
| | END OF COMMENTS: |
| | |