| Plan Review Notes For Permit 06040807 |
| Permit Number |
06040807 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-16 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 PLUMBING, CITY OF | | | WEST PALM BEACH AMENDMENTS TO FBC-2004, | | | CHAPTER 1, ADMINISTRATION. | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLUMBING PLAN REVIEW: | | | | | | 1. CHANGE UNDER SINK VENT TO READ AIR | | | ADMITTANCE VALVE PER FBC-2004 PLBG. SEC. | | | 917. | | | 2. PER CHAPTER 1, SEC. 106.1.1: SANITARY | | | PLBG. RISER DIAGRAM DOES NOT REFLECT THE | | | FLOOR PLAN. SHEET 3/3 FLOOR PLAN | | | INDICATES TWO 2" PVC UNDER SINK VENTS | | | WHICH SHOULD BE AIR ADMITTANCE VALVES | | | AND THE RISER DIAGRAM INDICATES ONE AIR | | | ADMITTANCE VALVE (A.A.V.) PLEASE | | | CORRELATE DRAWING | | | 3. CLEANOUTS REQUIRED AT BASE OF WASTE | | | STACKS AND NEAR THE JUNCTION OF THE | | | BUILDING DRAIN AND THE BUILDING SEWER, | | | PER FBC-2004 PLBG, SEC. 708.3.4 AND SEC. | | | 708.3.5. THE ISOMETRIC PLBG. RISER | | | DIAGRAM NEEDS TO INDICATE THE CLEANOUTS, | | | PLEASE SEE CORRECTED PLBG. SHEET 3/3 AND | | | CORRECT DRAWINGS BY DESIGN PROFESSIONAL | | | AND RESUBMIT. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|