Plan Review Notes
Plan Review Notes For Permit 06040807
Permit Number 06040807
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-16 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING, CITY OF
 WEST PALM BEACH AMENDMENTS TO FBC-2004,
 CHAPTER 1, ADMINISTRATION.
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. CHANGE UNDER SINK VENT TO READ AIR
 ADMITTANCE VALVE PER FBC-2004 PLBG. SEC.
 917.
 2. PER CHAPTER 1, SEC. 106.1.1: SANITARY
 PLBG. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. SHEET 3/3 FLOOR PLAN
 INDICATES TWO 2" PVC UNDER SINK VENTS
 WHICH SHOULD BE AIR ADMITTANCE VALVES
 AND THE RISER DIAGRAM INDICATES ONE AIR
 ADMITTANCE VALVE (A.A.V.) PLEASE
 CORRELATE DRAWING
 3. CLEANOUTS REQUIRED AT BASE OF WASTE
 STACKS AND NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER,
 PER FBC-2004 PLBG, SEC. 708.3.4 AND SEC.
 708.3.5. THE ISOMETRIC PLBG. RISER
 DIAGRAM NEEDS TO INDICATE THE CLEANOUTS,
 PLEASE SEE CORRECTED PLBG. SHEET 3/3 AND
 CORRECT DRAWINGS BY DESIGN PROFESSIONAL
 AND RESUBMIT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON