Plan Review Notes
Plan Review Notes For Permit 06040775
Permit Number 06040775
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-05 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE ELECTRICAL PLANS AND
 PERMIT APPLICATION IS NOW BEING
 SUBMITTED WITH BUILDING PERMIT. PLEASE
 KNOW, IT IS OK, FOR THE ELECTRICAL PLANS
 TO BE SUBMITTED WITH BUILDING , HOWEVER
 SINCE THE ELECTRICAL CONTRACTORWAS NOT
 SIGNED ON BUILDING CONTRACTORS ORIGINAL
 PERMIT APPLICATION, THE ELECTRICAL
 CONTRACTOR MAY COME IN AFTER BUILDING
 PERMIT IS ISSUED, REFERENCE THE BUILDIGN
 PERMIT AND AS LONG AS THE ELECTRICAL
 REVIEW IS "PASSED", THEN THE PERMIT IS
 DONE AS A TURNAROUND PERMIT.
 PLEASE SEETHE FOLLOWING ELECTRICAL
 COMMENTS.
  
 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR NEW ADDED LOADS ON HE EXISTING
 ELECTRICAL SERVICE.
 220.31
  
 3) NOTE: PLEASE SEE AN ADDITIONAL SWITCH
 IS BEING SHOWN ON THE PLANS FOR ??
 SOMETHING, BUT IT IS NOT SHOWN WHAT THIS
 IS SWITCHING.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  