2006-05-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE PLANS APPEAR CODE COMPLIANT
 WITH THE EXCEPTION OF THE WIND PRESSURES
 ON THE INSTALLATION SCHEDULE.HOW HAVE
 YOU DETERMINED PRESSURES LOWER THAN THE
 LOWEST FOUND ON FBC TABLE 1609.6B?IF
 YOU ARE USING ASCE7-02, ENGINEERING IS
 REQUIRED.YOU MAY ELIMINATE THAT COLUMN
 FROM THE CHART IF YOU DO NOT KNOW HOW TO
 FILL IT OUT AS YOUR ANCHORING IS
 COMPLIANT FOR UP TO -59.6.
  
 ALSO SHEET 4 HAS -29.67 HIGHLIGHTED.
 SEE FBC TABLE 1609.6B, TOO LOW FOR THIS
 WIND ZONE.