| 2006-07-12 00:00:00 | |
| | |
| | |
| | DENIED |
| | |
| | PREVIOUS NOTES NOT ADDRESSED: |
| | |
| | 6) PRODUCT APPROVAL FOR BUILT UP ROOFING |
| | DOES NOT ALLOW FOR ENHANCED FASTENING IN |
| | THE PERIMETER AND CORNER ZONES (SEE |
| | LIMITATION #9) AS SUCH THIS PRODUCT WILL |
| | NOT BE ACCEPTABLE (NOT ADDRESSED) |
| | |
| | 7) NOTE #5, SHT.1 STATES REPLACEMENT OF |
| | DOORS,FRAMES AND HARDWARE. PLEASE MARK |
| | NOA'S WITH DOOR TYPE USED, FRAME |
| | ATTACHMENT METHOD AND PROVIDE HARDWARE |
| | SCHEDULE (NOTE 5 STATES AL SERIES, |
| | PRODUCT APPROVAL D18 & E18) CLARIFY |
| | |
| | 9) NOTE #17, SHT.1 HC STALL WILL NOT |
| | MEET THE REQUIREMENTS FOR CLEAR FLOOR |
| | SPACE, LAVATORY ENCROACHES ON THE |
| | REQUIRED FLOOR SPACE FOR THE WATER |
| | CLOSET (SEE FIG. 30E IN CHAPTER 11 FBC) |
| | ( WILL NOT MEET FIXTURE COUNT, PROVIDE |
| | OCCUPANT LOAD FOR AREA) |
| | |
| | 10) THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | ( NEEDS APPROVAL OF DESIGNER OF RECORD) |
| | *************************************** |
| | |
| | 1) NOTE #9 SPECIFIES PGT WINDOWS NOT |
| | SHUTTERS AS SUBMITTED PRODUCT APPROVALS |
| | |
| | 2) NOTE #11 RECONDITIONING OF OLD |
| | SHUTTER OR NEW ? |
| | |
| | 3) SHUTTER NOA DOES NOT HAVE ATTACHMENT |
| | METHOD TO WOOD FRAMING, ONLY CONCRETE |
| | ATTACHMENT IS CONSIDERED |
| | |
| | 4) PROVIDE EXISTING FLOOR PLAN LAYOUT |
| | |
| | |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |