| Plan Review Notes For Permit 06040702 |
| Permit Number |
06040702 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-21 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE #4 CU PER 250.66 FOR 3/0 SERVICE | | | ENTRANCE CONDUCTORS. | | | | | | 2} THE CONTINUOUS LOADS IN THE PANEL | | | SCHEDULE MUST BE CALCULATED @ 125% PER | | | 210.20(A). | | | | | | 3} PLEASE COMPLETE THE INFORMATION IN | | | THE PANEL SPECIFICATION SECTION. | | | | | | IF THERE AER ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6731 |
|