| Date |
Text |
| 2006-05-09 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) PROVIDE WIND DESIGN CRITERIA PER |
| | 1603.1.4 FBC. SHOW COMPONENT AND |
| | CLADDING DESIGN PRESSURES TO DOORS AND |
| | WINDOWS |
| | |
| | 2) PROVIDE FRAMING DETAILS THAT SHOW |
| | ATTACHMENT/STRAPPING OF NEW DOUBLE 2X12 |
| | HEADERS AND SILLS ETC. ON PRESSBOX |
| | |
| | 3) PROVIDE PLAN VIEW OF PRESSBOX SHOWING |
| | WINDOW LAYOUT, GIVE SIZES AND AMOUNT OF |
| | WINDOWS, WILL THEY BE FRAMED |
| | INDIVIDUALLY OR USE PGT MULLIONS. |
| | |
| | 4) NO PRODUCT APPROVALS WERE SUBMITTED |
| | FOR WINDOWS OR MULLIONS IF USED. |
| | |
| | 5) PRODUCT APPROVAL FOR ROLL UP DOOR WAS |
| | SUBMITTED, WHERE IS THIS PRODUCT BEING |
| | USED? IT IS NOT ON DRAWINGS. ALSO IF |
| | PRODUCT IS TO BE INCORPORATED INTO |
| | DRAWING NEW UPDATED NOA WILL BE REQUIRED |
| | AS THIS ONE HAS EXPIRED |
| | |
| | 6) PRODUCT APPROVAL FOR BUILT UP ROOFING |
| | DOES NOT ALLOW FOR ENHANCED FASTENING IN |
| | THE PERIMETER AND CORNER ZONES (SEE |
| | LIMITATION #9) AS SUCH THIS PRODUCT WILL |
| | NOT BE ACCEPTABLE |
| | |
| | 7) NOTE #5, SHT.1 STATES REPLACEMENT OF |
| | DOORS,FRAMES AND HARDWARE. PLEASE MARK |
| | NOA'S WITH DOOR TYPE USED, FRAME |
| | ATTACHMENT METHOD AND PROVIDE HARDWARE |
| | SCHEDULE |
| | |
| | 8) NOTE #6, SHT.1 STATES REPLACEMENT OF |
| | TOILET PARTIONS WITH PLASTIC MATERIAL |
| | BUT DRAWING SHOWS U-BLOCK WALLS WITH HCM |
| | DOOR AS IN NOTE #5 PLEASE CLARIFY |
| | |
| | 9) NOTE #17, SHT.1 HC STALL WILL NOT |
| | MEET THE REQUIREMENTS FOR CLEAR FLOOR |
| | SPACE, LAVATORY ENCROACHES ON THE |
| | REQUIRED FLOOR SPACE FOR THE WATER |
| | CLOSET (SEE FIG. 30E IN CHAPTER 11 FBC) |
| | |
| | 10) THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 11) CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION,NATURE, AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | PER 106.1.1 FBC* (PROVIED LEGIBLE NOA'S |
| | THESE MUST BE READABLE FOR FIELD |
| | INSPECTIONS) |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |