Plan Review Notes
Plan Review Notes For Permit 06040695
Permit Number 06040695
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-24 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTE 1.
 2.SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN. (ONE RISER DIAGRAM MARKED IN
 RED.
 3.THE AUTOMATIC CLOTHES WASHER BRANCH
 DRAIN IS REQUIRED TO BE 3" PER FBC-2004
 PLUMBING SEC. 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695