| 2006-04-24 00:00:00 | ********** UNSAT ******** |
| | |
| | |
| | 1 )NOTE: PLEASE SEE PLANS MUST BE |
| | RE-SEALED AS THE SEAL AS SHOWN IS NO |
| | LONGER ACCEPTABLE AS PUBLIC RECORD FOR |
| | THE FLORIDA BOARD OF PROFESSINAL |
| | ENGINEER'S. PLEASE SEE FAC 61G15-23.001 |
| | WHICH IN FEB 04 CHANGED TO NOW REQUIRE |
| | ALL SEALS TO CONTAIN THE WORDING OF |
| | "LICENSE" AND COULD NO LONGER USE |
| | "CERTIFICATE". PLEASE KNOW, AN EXTENSION |
| | WAS GRANTED TO THE DATE OF 12/31/05 TO |
| | GIVE ALL ENGINEERS 2 YRS TO OBTAIN NEW |
| | SEALS. WE CAN NO LONGER ACCEPT OLD |
| | SEALS. |
| | THIS IS REQUIRED OF ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWERS. |
| | |
| | 2) NOTE: PLEASE LIST ALL THE REQUIRED |
| | ARC FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 2002 NEC. |
| | 210.12, REQUIRES ARC FAULT FOR ALL |
| | OUTLETS IN BEDRMS. (RECEPTS, LTS, FANS, |
| | SD'S ECT). |
| | |
| | 3) NOTE: PLEASE SEE MISSING GFI(S) ALONG |
| | KITCHEN COUNTER SPACE PER 210.52C1 |
| | |
| | 4) NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS FOR 2',6',12' RULE. |
| | PLEASE SEE REDLINED PLANS. |
| | |
| | |
| | 5) NOTE: PLEASE SEE BUILDING REVIEW |
| | COMMENTSWITH RESPECT TO VALUATION ON |
| | APPLIACTION. FBC ADMINISTRATIVE SECTION, |
| | 108.3 |
| | |
| | 6) NOTE: PLEASE SEE MISSING SD OUTSIDE |
| | MAST BEDRM. |
| | NFPA-72 2002, 11.5.1.1, 11.8.3.5 |
| | |
| | 7) NOTE: PLEASE DETAIL SEC'S FROM METER |
| | TO MCB PANEL, PLEASE KNOW, THESE MUST BE |
| | IN SLAB OR A MAIN WITH OCP WILL BE |
| | REQUIRED OUTSIDE AS NO MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS ARE PERMITTED IN |
| | DWELLING. 230.70. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |