2007-03-07 09:42:58*** PROVISO ***
 1) INSTALLATION OF OUTSIDE ABOVEGROUND TANKS. 7.9.2 A
 TANK OR TANKS WHOSE CAPACITY DOES NOT EXCEED 660 GAL
 (2500 L) SHALL BE PERMITTED TO BE INSTALLED OUTSIDE OF
 AND ADJACENT TO A BUILDING, PROVIDED THEY ARE SEPARATED
 FROM THE NEAREST LINE OF ADJOINING PROPERTY BY THE
 FOLLOWING MINIMUM DISTANCE:
 (1)5 FT (1.5 M) FOR TANKS NOT
 EXCEEDING 275 GAL (1040 L) CAPACITY
 (2)10 FT (3 M) FOR TANKS GREATER
 THAN 275 GAL (1040 L) CAPACITY, BUT NOT
 EXCEEDING 660 GAL (2500 L) CAPACITY.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
2007-03-02 18:59:18NEW SHEETS, NEEDS MECH STAMP.