Plan Review Notes
Plan Review Notes For Permit 06040674
Permit Number 06040674
Review Stop Z
Sequence Number 2
Notes
Date Text
2006-09-01 00:00:00BARBED WIRE MUST BE MOUNTED VERTICALLY
 OR AT AN ANGLE PROJECTING INTERIOR TO
 THE PROPERTY.
  
 A SURVEY SHOWING THE LOCATION OF THE
 GENERATOR MUST STILL BE PROVIDED.
  
 CHAINLINK FENCING IS NOT PERMITTED.
  
 OUTDOOR GENERATORS ARE SUBJECT TO THE
 SCREENING REQUIREMENTS FOUND IN SEC.
 94-444(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS. THIS SECTION
 READS AS FOLLOWS:
  
 (B)OUTDOOR STORAGE FOR NONRESIDENTIAL
 AND MULTIFAMILY USES; STORAGE AND
 DISPOSAL FACILITIES.OUTDOOR
 INCINERATORS, GARBAGE OR TRASH
 RECEPTACLES, FUEL OIL OR PROPANE TANKS,
 AND STORAGE RACKS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A
 FOUR-SIDED ENCLOSURE WITH AN OBSCURING
 GATE MAY BE REQUIRED AS A CONDITION FOR
 SITE PLAN APPROVAL. PLANS FOR THE LAYOUT
 OF TRASH RECEPTACLESSHALL BE IN
 ACCORDANCE WITH THE MINIMUM REQUIREMENTS
 SET FORTH IN FIGURE XIV-3. THE
 PROVISIONS OF THIS SECTION SHALL NOT
 APPLY TO LITTER CONTAINERS PROVIDED FOR
 THE CONVENIENCE OF PEDESTRIANS. ALL
 AREAS FOR THE STORAGE AND DISPOSAL OF
 TRASH AND GARBAGE SHALL BE PAVED WITH
 CONCRETE SURFACE AS REQUIRED BY THE CITY
 DEPARTMENT OF ENGINEERING AND PUBLIC
 WORKS.
  
 PLEASE CALL KELLY FREEMAN, PLANNER, AT
 (561) 822-1435 WITH ANY QUESTIONS.