2006-05-23 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTE #8.
  
 2) PLEASE SHOW IF BUILDING WALL NEXT TO
 GENERATOR IS MADE OF COMBUSTIBLE
 MATERIALS OR NOT. IF SO PLEASE COMPLY
 WITH NFPA 37 (4.1.4).
  
 3) PLEASE SHOW LOCATION OF GENERATOR AND
 ADJOINING PROPERTY LINES ON PLANS.
  
 4) PLEASE BE ADVISED, INSTALLATION OF
 OUTSIDE ABOVEGROUND TANKS.
 7.9.2 A TANK OR TANKS WHOSE CAPACITY
 DOES NOT EXCEED 660 GAL (2500 L) SHALL
 BE PERMITTED TO BE INSTALLED OUTSIDE OF
 AND ADJACENT TO A BUILDING, PROVIDED
 THEY ARE SEPARATED FROM THE NEAREST LINE
 OF ADJOINING PROPERTY BY THE FOLLOWING
 MINIMUM DISTANCE:
 (1)5 FT (1.5 M) FOR TANKS NOT
 EXCEEDING 275 GAL (1040 L) CAPACITY
 (2)10 FT (3 M) FOR TANKS GREATER
 THAN 275 GAL (1040 L) CAPACITY, BUT NOT
 EXCEEDING 660 GAL (2500 L) CAPACITY
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.