| Plan Review Notes For Permit 06040674 |
| Permit Number |
06040674 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-23 00:00:00 | *** DENIED *** | | | 1) PLEASE SEE ELECTRICAL REVIEW NOTE #8. | | | | | | 2) PLEASE SHOW IF BUILDING WALL NEXT TO | | | GENERATOR IS MADE OF COMBUSTIBLE | | | MATERIALS OR NOT. IF SO PLEASE COMPLY | | | WITH NFPA 37 (4.1.4). | | | | | | 3) PLEASE SHOW LOCATION OF GENERATOR AND | | | ADJOINING PROPERTY LINES ON PLANS. | | | | | | 4) PLEASE BE ADVISED, INSTALLATION OF | | | OUTSIDE ABOVEGROUND TANKS. | | | 7.9.2 A TANK OR TANKS WHOSE CAPACITY | | | DOES NOT EXCEED 660 GAL (2500 L) SHALL | | | BE PERMITTED TO BE INSTALLED OUTSIDE OF | | | AND ADJACENT TO A BUILDING, PROVIDED | | | THEY ARE SEPARATED FROM THE NEAREST LINE | | | OF ADJOINING PROPERTY BY THE FOLLOWING | | | MINIMUM DISTANCE: | | | (1)5 FT (1.5 M) FOR TANKS NOT | | | EXCEEDING 275 GAL (1040 L) CAPACITY | | | (2)10 FT (3 M) FOR TANKS GREATER | | | THAN 275 GAL (1040 L) CAPACITY, BUT NOT | | | EXCEEDING 660 GAL (2500 L) CAPACITY | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|