Plan Review Notes
Plan Review Notes For Permit 06040674
Permit Number 06040674
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-09 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS DETAIL FOR SLAB. COULD NOT LOCATE ON
 PLANS.
  
 2)NOTE: PLEASE SEE CURRENT CODES NEED TO
 BE REFERENCED ON PLANS. PLEASE SEE THAT
 WE ARE CURRENLTY UNDER THE 2004 FBC,
 2003 NFPA-101, 2002 NFPA-110, 2002
 NFPA-70
  
 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 WITH RESPECT TO BFE IF IN A FLOOD ZONE.
 PLEASE SEE NFPA-110 7.2.3*
 PLEASE NOTE AND VERIFY THE LOCATION OF
 GENERATOR.
  
 4)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GEN, ATS, SUB BASE
 FUEL TANK, WP HOUSING.
 PLEASE SEE THE SPECS SUBMITTED DO NOT
 CORRELATE WITH PLANS. ATS, GEN
 PLEASE ALSO "HIGHLIGHT" AND INDICATE
 UNITS BEING INSTALDLLED ON SPECS.
  
 5)NOTE: PLEASE SEE EXISTING MCB IS SHOWN
 ON ROOF???
 PLEASE VERIFY AS THIS IS NOT READILY
 ACCESSIBLE AS REQUIRED PER 230.70,PLEASE
 SEE MAINS ARE NOT GROUPED PER 230.72,
 225.34, 225.31-225.39
 PLEASE SHOW AND INDICATE THE LOCATION OF
 EXISTING SERVICE FOR BUILDING AND MAINS.
  
 6)NOTE: PLEASE SEE VALUATION IS BASED ON
 COMPLETE SCOPE PF WORK WHICH IS TO
 INCLUDE ALL LABOUR AND MATERIALS, EVEN
 OF ANY EQUIPMENT IS OWNER SUPPLIED.
 VALUE AS SHOWN IS WAY LOW AND MAY BE
 ADJUSTED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INCREASED.
 THIS IS TO BE INCREASED WHEN
 RESUBMITTING PLANS AFTER ALL REVIEWS ARE
 COMPLETED.
  
 7)NOTE: PLEASE SUBMIT THE INTENDED LOADS
 FOR GENERATOR. GEN MUST BE SIZED FOR
 LOADS SERVED. PLEASE SEE LOAD SUMMARY
 PROVIDED IS REQUIRED TO BE SIGNED, DATED
 AND SEAL BY SIAD ENGINEER OF RECORD.
 220, 215.5
  
 ***
 8) NOTE: PLEASE SEE PLANS CONTAIN A
 "RAISED SEAL" ON PLANS WHICH CONTAIN A
 "PHOTO-COPIED" SIGNATURE. PLEASE SEE
 THISH HAS BEEN NOTED ON SOME OTHER
 PROJECTS AND PLANS ARE STILL BEING THE
 SAME WAY. PLEASE SEE FS 471.025 AND FAC
 61G15-23.002 WHICH REQUIRES THE
 "ORIGINAL" SIGNATURE. PLEASE KNOW, ONE
 COPY OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW