| 2006-05-09 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | AS DETAIL FOR SLAB. COULD NOT LOCATE ON |
| | PLANS. |
| | |
| | 2)NOTE: PLEASE SEE CURRENT CODES NEED TO |
| | BE REFERENCED ON PLANS. PLEASE SEE THAT |
| | WE ARE CURRENLTY UNDER THE 2004 FBC, |
| | 2003 NFPA-101, 2002 NFPA-110, 2002 |
| | NFPA-70 |
| | |
| | 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | WITH RESPECT TO BFE IF IN A FLOOD ZONE. |
| | PLEASE SEE NFPA-110 7.2.3* |
| | PLEASE NOTE AND VERIFY THE LOCATION OF |
| | GENERATOR. |
| | |
| | 4)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS/CUT SHEETS FOR GEN, ATS, SUB BASE |
| | FUEL TANK, WP HOUSING. |
| | PLEASE SEE THE SPECS SUBMITTED DO NOT |
| | CORRELATE WITH PLANS. ATS, GEN |
| | PLEASE ALSO "HIGHLIGHT" AND INDICATE |
| | UNITS BEING INSTALDLLED ON SPECS. |
| | |
| | 5)NOTE: PLEASE SEE EXISTING MCB IS SHOWN |
| | ON ROOF??? |
| | PLEASE VERIFY AS THIS IS NOT READILY |
| | ACCESSIBLE AS REQUIRED PER 230.70,PLEASE |
| | SEE MAINS ARE NOT GROUPED PER 230.72, |
| | 225.34, 225.31-225.39 |
| | PLEASE SHOW AND INDICATE THE LOCATION OF |
| | EXISTING SERVICE FOR BUILDING AND MAINS. |
| | |
| | 6)NOTE: PLEASE SEE VALUATION IS BASED ON |
| | COMPLETE SCOPE PF WORK WHICH IS TO |
| | INCLUDE ALL LABOUR AND MATERIALS, EVEN |
| | OF ANY EQUIPMENT IS OWNER SUPPLIED. |
| | VALUE AS SHOWN IS WAY LOW AND MAY BE |
| | ADJUSTED BY THIS OFFICE IF AN |
| | APPROPRIATE VALUE IS NOT INCREASED. |
| | THIS IS TO BE INCREASED WHEN |
| | RESUBMITTING PLANS AFTER ALL REVIEWS ARE |
| | COMPLETED. |
| | |
| | 7)NOTE: PLEASE SUBMIT THE INTENDED LOADS |
| | FOR GENERATOR. GEN MUST BE SIZED FOR |
| | LOADS SERVED. PLEASE SEE LOAD SUMMARY |
| | PROVIDED IS REQUIRED TO BE SIGNED, DATED |
| | AND SEAL BY SIAD ENGINEER OF RECORD. |
| | 220, 215.5 |
| | |
| | *** |
| | 8) NOTE: PLEASE SEE PLANS CONTAIN A |
| | "RAISED SEAL" ON PLANS WHICH CONTAIN A |
| | "PHOTO-COPIED" SIGNATURE. PLEASE SEE |
| | THISH HAS BEEN NOTED ON SOME OTHER |
| | PROJECTS AND PLANS ARE STILL BEING THE |
| | SAME WAY. PLEASE SEE FS 471.025 AND FAC |
| | 61G15-23.002 WHICH REQUIRES THE |
| | "ORIGINAL" SIGNATURE. PLEASE KNOW, ONE |
| | COPY OF PLANS ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |