Notes
Date Text
2006-06-16 00:00:001. SITE PLAN DOES NOT ILLUSTRATE ANY NEW
 OR EXISTING FIRE HYDRANTS. PLEASE
 DISPLAY NECESSARY INFORMATION.
  
 2. PLEASE INDICATE OCCUPANCY TYPE AND
 AND PROPOSED OCCUPANT LOAD FOR PERMITTED
 AREA.
  
 3. ARE ANY IDENTIFIERS OR ADDRESS
 PLANNED TO LOCATE THIS AREA SHOULD AN
 EMERGENCY DEVELOP. NO INFORMATION SHOWN
 ON ANY OF THE ELEVATIONS.
  
 4. NO PORTABLE FIRE EXTINGUISHER SHOWN
 ON THE DRAWINGS.
  
 5. PLEASE EXPLAIN CONROL ROOM NOTE. THE
 CONTROL ROOM IS USED FOR WHAT PURPOSE
 AND FOR WHAT SPECIFIC AREA.
  
 6. DEMOLITION, CONTRUCTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  