Plan Review Notes
Plan Review Notes For Permit 06040670
Permit Number 06040670
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-17 00:00:00*** UNSAT ***
  
 PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND AHVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE SEE 240.21 FOR WHAT
 APPEARS TO BE "TAPPED" CONDUCTORS FROM
 THE 600A MAIN DISCONNECT AS SHOWN TO
 X-FORMER AND NEW PANEL "L".
 PLEASE ALSO CLARIFY THE TAP FOR OTHER
 EXIST CONTROL PANEL.
 240.4,310.16.
 DOES THIS EXISTING 600A MAIN SERVICE
 DISCONNECT CONTAIN OCP FOR THE
 TRANSFORMER?
 THE SCENERIO IS UNCLEAR AT THIS TIME.
  
 2) NOTE: PLEASE SEE CIRCUITING FOR EXT
 LT NOT SHOWN.
 THIS ITEM COULD BE REDLINHED, HOWEVER
 PLANS HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
  
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  