| Plan Review Notes For Permit 06040670 |
| Permit Number |
06040670 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-17 00:00:00 | *** UNSAT *** | | | | | | PLEASE KNOW, PLANS HAVE ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW" AND AHVE NOT | | | BEEN SUBMITTED FOR PERMIT. | | | | | | 1) NOTE: PLEASE SEE 240.21 FOR WHAT | | | APPEARS TO BE "TAPPED" CONDUCTORS FROM | | | THE 600A MAIN DISCONNECT AS SHOWN TO | | | X-FORMER AND NEW PANEL "L". | | | PLEASE ALSO CLARIFY THE TAP FOR OTHER | | | EXIST CONTROL PANEL. | | | 240.4,310.16. | | | DOES THIS EXISTING 600A MAIN SERVICE | | | DISCONNECT CONTAIN OCP FOR THE | | | TRANSFORMER? | | | THE SCENERIO IS UNCLEAR AT THIS TIME. | | | | | | 2) NOTE: PLEASE SEE CIRCUITING FOR EXT | | | LT NOT SHOWN. | | | THIS ITEM COULD BE REDLINHED, HOWEVER | | | PLANS HAVE NOT BEEN SUBMITTED FOR | | | PERMIT. | | | | | | | | | PLEASE SEE ANY OTHER COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELEECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|