Plan Review Notes
Plan Review Notes For Permit 06040669
Permit Number 06040669
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-18 00:00:00 
  
 DENIED
  
 1) FLORIDA COVER SHEET ROOF SHINGLES IS
 FOR 2001 CODE, PLEASE SUBMIT 2004 COVER.
 THE NOA IS THE SAME AND IS OK TO SUBMIT
 WITH NEW COVER
  
 2) CHOSEN SYSTEM FOR FLAT ROOF HAS A PSF
 -45 AND A LIMITATION #9 WHICH DOES NOT
 ALLOW FOR ENHANCED FASTENING (SEE PAGE
 30 OF NOA). OTHER SYSTEMS IN THIS NOA
 USE LIMITATION #7 AND THOSE REQUIRE
 CALCULATIONS TO BE PREPARED BY AN
 ENGINEER,ARCHITECT OR ROOFING CONSULTANT
  
 BLDG PLAN REVIEW