| Notes |
| Date |
Text |
| 2006-05-26 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.)IT APPEARS FROM MY PREVIOUS COMMENT | | | THAT THERE WAS A DIFFERENT PRODUCT | | | APPROVAL IN THE PACKAGE FIRST REVIEW. | | | THIS MAY BE WHY THERE ARE DIFFERENT | | | COMMENTS. | | | | | | 2.)THE SCHEDULE SPECIFIES 12 AND 24 | | | INCH SPACING ON A SCHEDULE.SHEET 3 YOU | | | HAVE CIRCLED 9" SPACING.THE OTHER | | | TABLE ON THE SAME SHEET INDICATES THAT | | | 9" SPACING IS FOR 37PSF, NOT COMPLIANT | | | FOR YOUR APPLICATION AND THE DESIGN | | | PRESSURE YOU HAVE DECLARED (47PSF, 40 FT | | | HIGH BUILDING). |
|