| 2006-07-07 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED |
| | ITEMS APPLY |
| | |
| | FROM PREVIOUS LIST |
| | |
| | _XX_2.PROVIDE BUILDING HEIGHT |
| | CERTIFICATION PREPARED BY AN ENGINEER OR |
| | ARCHITECT.THIS IS REQUIRED AS ALL OF |
| | YOUR PERMIT APPLICATIONS HAVE A DECLARED |
| | BUILDING HEIGHT OF 15' DESPITE THE FACT |
| | THAT ONE IS A HIGH RISE.IF THE |
| | BUILDING IS OVER 60' DESIGN PRESSURES |
| | BASED ON ASCE7-02 PREPARED BY AN |
| | ENGINEER WILL ALSO BE REQUIRED. |
| | |
| | 2ND REVIEW - THE BUILDING HEIGHT IS |
| | DECLARED AS 120' ON BOTH THE |
| | INSTALLATION SCHEDULE AND ON THE |
| | COMPUTERIZED ENGINEERING. |
| | |
| | ENGINEERING MUST BE SIGNED, SEALED, |
| | DATED ORIGINALS PREPARED BY A FLORIDA |
| | PROFESSIONAL ENGINEER.THIS IS REQUIRED |
| | ONLY FOR BUILDINGS OVER 60'.BASED ON |
| | THE INFORMATION PROVIDED, ENGINEERING IS |
| | REQUIRED.PLEASE CONFIRM BUILDING |
| | HEIGHT. |
| | |
| | NEW COMMENT: |
| | |
| | PROVIDE A COPY OF THE CONDO ASSOCIATION |
| | APPROVAL. |