2006-07-15 00:00:00DENIED;
 1. (SECOND REQUEST) DELETE THE PART OF
 NOTE # 8 ON PAGE P.201 REFYING TO AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED
 ENGINEERED PRODUCTAND THEY DON"T WORK.
 2.(SECOND REQUEST) A TWO WAY CLEANOUT IS
 REQUIRED IN THE DRAINAGE SYSTEM AT THE
 JUNSION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER. SEE SEC 708.3.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695