| Plan Review Notes For Permit 06040636 |
| Permit Number |
06040636 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-29 00:00:00 | DENIED; | | | 1. DELETE OR CHANGE NOTE #8. WATER | | | HAMMER ARRESTORS ARE REQUIRED WHERE | | | QUICK CLOSING VALUES ARE USED, @ | | | AUTOMATIC CLOTHES WASHER, DISHWASHER, | | | AND ICE MAKERS. SEE FBC-2004 PLUMBING | | | SEC. 604.9. | | | 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN | | | TO BE 3" SEC. 406.3 AND A CLEAN OUT IN | | | THE VENT STACK AT 48" AFF. | | | 3.A TWO WAY CLEAN OUT IS REQUIRED AT THE | | | JUNCTION OF THE BUILDING DRAIN AND THE | | | BUILDING SEWER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|