| Plan Review Notes For Permit 06040635 |
| Permit Number |
06040635 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-12 00:00:00 | DENIED; | | | 1.(SECOND REQUEST) DELETE THE PART OF | | | NOTE 8 ON PAGE P.201 REFURING TO AIR | | | CHAMBERS. AIR CHAMBERS ARE NOT AN | | | APPROVED ENGINEEREDPRODUCT AND DO NOT | | | WORK. | | | 2.(SECOND REQUEST) A TWO WAY CLEANOUT IS | | | REQUIRED IN THE DRAINAGE SYSTEM AT THE | | | JUNSION OF THE BUILING DRAIN AND THE | | | BUILDING SEWER PER FBC-2004 PLUMBING | | | SEC. 708.3.5. | | | 3.REVISION AREA OF TITLE BLOCK; THE LAST | | | REVISION ON SHEET IS 7 ON PLANS THERE IS | | | REFORENCE TO 8 PLEASE UP DATE PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|