| Notes |
| Date |
Text |
| 2006-07-12 00:00:00 | DENIED | | | | | | 1) SHEET A1.0 DOES NOT HAVE A TITLE | | | BLOCK. FAC 61G1-16.004 A TITLE BLOCK | | | MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND | | | SPECIFICATION IDENTIFICATION SHEETS. | | | | | | 2) FBC TABLE 1607.1 REQUIRES TRUSSES TO | | | HAVE A MINIMUM BOTTOM CORD LIVE LOAD OF | | | 10 PSF. A BC LIVE LOAD OF 0.0 PSF IS | | | SPECIFIED ON THE TRUSS DRAWINGS. THE | | | TRUSS COVERSHEET SPECIFIES 10 PSF. | | | | | | 3) THE BOTTOM CORD DEAD LOAD IS | | | SPECIFIED AS 5 PSF ON THE TRUSS | | | COVERSHEET AND 15 PSF ON THE TRUSS | | | DRAWINGS. | | | | | | 4) THE TRUSS COVERSHEET REFERENCES THE | | | 2001 FBC. THE PROJECT IS UNDER THE 2004 | | | FBC. | | | | | | NOTE: IMPACT FEES AND NOC WILL BE | | | REQUIRED FOR EACH PERMIT APPLIED FOR | | | UNDER THE MASTER. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|