Plan Review Notes
Plan Review Notes For Permit 06040635
Permit Number 06040635
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-12 00:00:00DENIED
  
 1) SHEET A1.0 DOES NOT HAVE A TITLE
 BLOCK. FAC 61G1-16.004 A TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND
 SPECIFICATION IDENTIFICATION SHEETS.
  
 2) FBC TABLE 1607.1 REQUIRES TRUSSES TO
 HAVE A MINIMUM BOTTOM CORD LIVE LOAD OF
 10 PSF. A BC LIVE LOAD OF 0.0 PSF IS
 SPECIFIED ON THE TRUSS DRAWINGS. THE
 TRUSS COVERSHEET SPECIFIES 10 PSF.
  
 3) THE BOTTOM CORD DEAD LOAD IS
 SPECIFIED AS 5 PSF ON THE TRUSS
 COVERSHEET AND 15 PSF ON THE TRUSS
 DRAWINGS.
  
 4) THE TRUSS COVERSHEET REFERENCES THE
 2001 FBC. THE PROJECT IS UNDER THE 2004
 FBC.
  
 NOTE: IMPACT FEES AND NOC WILL BE
 REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER.
  