2006-04-28 00:00:00*** MODEL B ***
 1) DRYER VENT TERMINATION MUST BE A MIN.
 OF 4 FEET FROM A/C CONDENSER UNIT.
  
 2) SUPPLY AIR GRILLS NEED TO BE SIZED,
 KITCHEN, AND EACH BATH ROOM.
  
 3) RETURN AIR GRILLS NEED TO BE SIZED,
 ALL.
  
 4) SUPPLY AIR DUCT FROM AHU TO MIXING
 BOX NEEDS TO SHOW THE SIZED.
  
 5) NEED TO SHOW THE CFM'S AT ALL SUPPLY
 AIR GRILLS.
  
 6) PROVIDE RETURN AIR TO THE AHU, BY
 LOUVER DOOR, OR RETURN AIR GRILL
 (SHOWING SIZE).
  
 7) PLEASE SHOW EQUIPMENT LISTING WITH
 MAKE, MODEL NUMBER, TONS, SEER, TOTAL
 COOLING BTU'S, TOTAL SENSIBLE BTU'S, AND
 HEATER KW..
  
 8) PLEASE BE ADVISED 10 SEER IS
 ACCEPTABLE AT THIS TIME, BUT MAY NOT BE
 IN THE FUTURE.
  
 9) PLEASE BE ADVISED 6" DUCT MAY BE TO
 LARGE FOR THE BATH ROOMS.
  
 10) PLEASE SEE NOTATIONS ON MECHANICAL
 PLANS.
  
 11) MANUAL J CALCULATIONS ARE MISSING,
 PLEASE SUBMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.