| Plan Review Notes For Permit 06040635 |
| Permit Number |
06040635 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-28 00:00:00 | *** MODEL B *** | | | 1) DRYER VENT TERMINATION MUST BE A MIN. | | | OF 4 FEET FROM A/C CONDENSER UNIT. | | | | | | 2) SUPPLY AIR GRILLS NEED TO BE SIZED, | | | KITCHEN, AND EACH BATH ROOM. | | | | | | 3) RETURN AIR GRILLS NEED TO BE SIZED, | | | ALL. | | | | | | 4) SUPPLY AIR DUCT FROM AHU TO MIXING | | | BOX NEEDS TO SHOW THE SIZED. | | | | | | 5) NEED TO SHOW THE CFM'S AT ALL SUPPLY | | | AIR GRILLS. | | | | | | 6) PROVIDE RETURN AIR TO THE AHU, BY | | | LOUVER DOOR, OR RETURN AIR GRILL | | | (SHOWING SIZE). | | | | | | 7) PLEASE SHOW EQUIPMENT LISTING WITH | | | MAKE, MODEL NUMBER, TONS, SEER, TOTAL | | | COOLING BTU'S, TOTAL SENSIBLE BTU'S, AND | | | HEATER KW.. | | | | | | 8) PLEASE BE ADVISED 10 SEER IS | | | ACCEPTABLE AT THIS TIME, BUT MAY NOT BE | | | IN THE FUTURE. | | | | | | 9) PLEASE BE ADVISED 6" DUCT MAY BE TO | | | LARGE FOR THE BATH ROOMS. | | | | | | 10) PLEASE SEE NOTATIONS ON MECHANICAL | | | PLANS. | | | | | | 11) MANUAL J CALCULATIONS ARE MISSING, | | | PLEASE SUBMIT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|