| 2006-04-27 00:00:00 | ***** UNSAT ***** | | | | | | MODEL "B" | | | | | | 1) NOTE: PLEASE SUBMIT THE AIC RATING | | | FOR THE NEW SERVICE MAINS(S). | | | 110.9,215.5 | | | ALL SERVICE EQUIPMENT SHALL BE RATED FOR | | | THE AVAILABLE FAULT CURRENT. | | | | | | 2) NOTE: PLEASE SEE GENERAL NOTES, #5 | | | WHICH MENTIONS "ALL RECEPTICALES" IN | | | BEDRMS, THE WORDING PER 2002 NEC 210.12 | | | SHOULD READ ALL, "OUTLETS " IN BEDRMS. | | | IF THERE ARE ANY QUESTIONS, ON THIS | | | PLEASE CALL. | | | | | | 3) NOTE: PLEASE SEE WALL IN LIVING ROOM | | | WHICH SHOULD INDICATE THE RECEPT WITHIN | | | 6' OF DOOR OPENING. | | | PLEASE SEE REDLINED SET. | | | | | | ** PLEASE KNOW, THESE ARE FOR "MASTERS" | | | AND ALL MUST BE 100%. | | | | | | PLEASE CALL IF THERE ARE ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|