Plan Review Notes
Plan Review Notes For Permit 06040635
Permit Number 06040635
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-27 00:00:00***** UNSAT *****
  
 MODEL "B"
  
 1) NOTE: PLEASE SUBMIT THE AIC RATING
 FOR THE NEW SERVICE MAINS(S).
 110.9,215.5
 ALL SERVICE EQUIPMENT SHALL BE RATED FOR
 THE AVAILABLE FAULT CURRENT.
  
 2) NOTE: PLEASE SEE GENERAL NOTES, #5
 WHICH MENTIONS "ALL RECEPTICALES" IN
 BEDRMS, THE WORDING PER 2002 NEC 210.12
 SHOULD READ ALL, "OUTLETS " IN BEDRMS.
 IF THERE ARE ANY QUESTIONS, ON THIS
 PLEASE CALL.
  
 3) NOTE: PLEASE SEE WALL IN LIVING ROOM
 WHICH SHOULD INDICATE THE RECEPT WITHIN
 6' OF DOOR OPENING.
 PLEASE SEE REDLINED SET.
  
 ** PLEASE KNOW, THESE ARE FOR "MASTERS"
 AND ALL MUST BE 100%.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]