Plan Review Notes
Plan Review Notes For Permit 06040635
Permit Number 06040635
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-10 00:00:00DENIED BY BUILDING
  
 1) SUBMIT A TYPICAL DRAINAGE PLAN
 SHOWING COMPLIANCE WITH 2004 FBC R401.3.
 INDIVIDUAL DRAINAGE PLANS WILL BE
 REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE PROJECT.
  
 2) IMPACT FEES AND NOC WILL BE REQUIRED
 FOR EACH PERMIT UNDER PROJECT.
  
 3) THE WALL SECTION ON S2.01 SPECIFIES
 TWO COURSES OF BOND BEAM WITH ONE #7 IN
 EACH COURSE. THE BEAM SCHEDULE ON S2.02
 INDICATES ONE #5 IN EACH COURSE. PLEASE
 CORRECT.
  
 4) THE ENERGY CALCULATION FORM IS
 REQUIRED TO USE WORST-CASE CALCULATIONS
 FOR A MASTER PROJECT. SEE FBC
 13-600.2.A.5.
  
 5) THE TRUSS ENGINEER'S EMBOSSED STAMP
 IS REQUIRED TO HAVE THE WORDING CHANGED
 FROM "CERTIFICATE" TO "LICENSE".
  
 6) FBC TABLE 1607.1 REQUIRES TRUSSES TO
 HAVE A MINIMUM BOTTOM CORD LIVE LOAD OF
 10 PSF.
  
 7) THE DESIGN LOAD SCHEDULE ON S2.03,
 THE DESIGN LOADS ON THE TRUSS DRAWINGS
 AND THE DESIGN LOAD ON THE TRUSS LAYOUT
 DO NOT CONCUR. PLEASE CORRECT.
  
 8) THE UPLIFT FOR TRUSSES T2B, T3B AND
 T4B AT BEARING POINTS R1 AND R4 HAVE
 UPLIFTS ON THE ENDS THAT EXCEED THOSE
 LISTED ON S2.03.
  
 9) TRUSS T6 HAS AN UPLIFT OF 636# ON THE
 LEFT END WHICH EXCEEDS THE 510# LISTED
 ON S2.03.
  
 10) SUBMIT FLORIDA PRODUCT APPROVAL FOR
 THE "USP" THD210-2 HANGER.
  
 11) THE TABLE ON S3.01 SPECIFIES
 ALUMINUM SOFFITS AND THE SECTION ON
 S2.01 INDICATES STUCCO ON METAL LATH AT
 THE SOFFIT. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714