| 2006-08-04 00:00:00 | ****** UNSAT2ND REVIEW ******** |
| | |
| | ** PLEASE SEE SOME OF THE NOTES FROM |
| | PREVIOUS REVIEW STILL NEED TO BE |
| | ADDRESSED. |
| | PLEASE ALSO SEE NEW COMMENT FOR HAND |
| | WRITTEN ITEMS ON PLANS. |
| | |
| | 1) NOTE:NO , PLEASE SEE ALL OLD/VOIDED |
| | SHEETS WERE LEFT IN SETS WHEN REQUESTED |
| | TO BE REMOVED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO COMPLETELY |
| | REMOVED ANY OF THE OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT THE NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | THIS WILL HELP TO AVOID ANY DELAYS IN |
| | PROCESSING PROJECT. |
| | ** ONE COPY OF ANY OLD/VOIDED REMOVED |
| | SHEETS SHOULD BE SUBMITTED SEPARATELY |
| | FOR REFERENCE. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE:NO, NOTE MENTIONS ALL ADOPTED |
| | CODES, HOWEVER PLEASE SEE THAT THE CODES |
| | RELEVANT TO DESIGN SHALL BE SPECIFIC AND |
| | ON PLANS.PLEASE SEE MIN CODES WHICH WERE |
| | GIVEN BELOW TO BE STATED ON ELECTRICAL |
| | PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS SHALL |
| | REFERENCE THE CURRENT CODES IN EFFECT. |
| | PLEASE SEE PLANS NOW INDICATE THE |
| | "LATEST CODES". WE ARE NOT CURRENTLY |
| | UNDER THE LATEST CODES AS THEY HAVE NOT |
| | YET BEEN ADOPTED BY THE STATE OF |
| | FLORIDA. |
| | PLEASE SEE THE FOLLOWING AT A MIN SHOULD |
| | BEON PLANS. 2002 NFPA-70, 2003 NFPA-101, |
| | 2002 NFPA-72. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. SEE NEW NOTES. |
| | |
| | 8) NOTE: NO? PLEASE SEE LOAD |
| | CALCULATIONS MENTIONS A LOAD FOR PANEL |
| | "C" HOWEVER HOW AND WHERE ARE LOADS |
| | DERIVED. PLEASE SEE AS NOTED ON PREVIOUS |
| | NOTE, PLEASE INDICATE THE LOADS(DRYER, |
| | WASHER, SM APPLIANCE CIRCUITS, ETC |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE LOAD CALCULATIONS |
| | SHALL INCLUDE ALL LOADS ON EXISTING |
| | PANEL "C" AS THIS EXISTING PANEL "C" IS |
| | BEING FED FROM NEW 225A MAIN, YET LOAD |
| | CALCULATIONS ON SHOW NEW HOUSE PANEL |
| | LOADS. |
| | 215.5,220.31B. UNABLE TO VERIFY MANY |
| | ITEMS FROM EXISTING PANEL AND LOADS AT |
| | THIS TIME. PLEASE SEE NEC FOR MIN LOADS |
| | REQUIRED FOR DRYER AND WASHER/LAUNDRY. |
| | 220.18, 220.16 ETC. |
| | |
| | 9) NOTE: NO, PLEASE SEE ROOM WHICH IS |
| | BEING IDENTIFIED AT "PANTRY" A RECEPT |
| | WAS REDLINED FOR WALL SPACE AS THIS IS |
| | BEING SHOWN AS A ROOM. IF THIS IS A |
| | "HALL" THEN ADJUST ACCORDINGLY. |
| | PLEASE SEE BEDRM UPSTAIRS AS PREVIOUS |
| | PLANS WERE REDLINED FOR MORE THAN 2' OF |
| | WALL IN BEDRM #1 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEEPLEASE SEE MISSING RECEPTS |
| | PER |
| | 210.52 |
| | |
| | 10) NOTE:NO, PLEASE SEE PREVIOUS PLANS |
| | WERE REDLINE WHERE THIS WOULD BE |
| | REQUIRED. PLEASE SEE COUNTER IS OVER 8' |
| | WHICH WOULD REQUIRE 3 COUNTER SPACE |
| | RECEPTS. |
| | PLEASE SEE THE THIRD RECEPT SHOWN IS FOR |
| | THE DISPOSAL. |
| | PLEASE SEE PLANS ARE REDLINED ONCE AGAIN |
| | AT THAT LOCATION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING GFI RECEPT |
| | ALONG KITCHEN COUNTER SPACE PER |
| | 210.52C1,210.8A6. |
| | |
| | 11) NOTE:OK/NO, WATER HEATER IS NOW |
| | BEING SHOWN W/ 2500W HEAT, HOWEVER CAN |
| | NOT VERIFY THE LOAD AS THIS IS NOT |
| | PLACED IN LOAD CALCULATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY WATER HEATER, |
| | NEW , EXISTING ETC. NOWATER HEATER IS |
| | SHOWN ON ELECTRICAL PLANS. THIS IS SHOWN |
| | ON "P" SHEETS, HOWEVER THE LOAD SHALL |
| | ALSO BE INCLUDED WITH LOAD CALCULATIONS |
| | FOR SERVICE. |
| | 215.5, 220.31B |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: OK. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16)NOTE:NO, ONLY SHOWN FOR PANELS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 17) NOTE: NO, THIS IS THE SAME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER IS SHOWING |
| | "EQUIPMENT GROUNDING CONDUCTORS" FROM |
| | METER TO MAINS. PLEASE SEE THE EQP GRNDS |
| | ARE ONLY INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | 250.6,250.24B |
| | |
| | 18) NOTE: OK. |
| | |
| | 19) NOTE: STILL SHOWING THE FOOTER STEEL |
| | AT EXISTING GUEST HOUSE? THIS IS OK. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE GROUNDING ELECTRODE |
| | RISER AT GUEST HOUSE WHICH INDICATES |
| | FOOTER STEEL? PLEASE KNOW, AS AN |
| | EXSITING BUILDING, THIS IS NOT REQUIRED |
| | AT GUEST HOUSE , ONLY MAIN HOUSE. PLEASE |
| | KNOW, THE STRUCTURAL INTEGRITY OF THE |
| | EXISTING FOOTER MAY BE COMPOMISED TO |
| | ATTACH. PLEASE KNOW, GIVEN THE AGE OF |
| | THE EXISTING FOOTER IN THIS GUEST HOUSE, |
| | FOOTER STEEL MAY NOT BE PRESENT AT |
| | ALL.?? |
| | THIS IS FOR INFORMATION ONLY AS, IT MAY |
| | BE DONE, BUT NOT REQUIRED AT GUEST |
| | HOUSE. |
| | |
| | 20) NOTE:NO, PLEASE SEE A NOTE WAS |
| | ADDED TO ONLY ONE. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE DISCONNECT AND AHU |
| | IN CLOSETS SEEMS TO BE LOCATED |
| | NOT TO MEET 110.26 AND THE MECHANICAL |
| | CODE. |
| | PLEASE ALSO SEE 240.24D AS OCP IS NOT |
| | PERMITTED IN A CLOTHES/STORAGE CLOSET. |
| | PLEASE SEE THIS LOCATION AND THE CLOSE |
| | PROXIMITY TO EASILY IGNITIBLE MATERIALS. |
| | |
| | 21) NOTE: OK. |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE:NO, PLEASE SEE OCP ON SOME |
| | UNITS ON PANEL SCHEDULE EXCEED THE MAX |
| | OCP RATING AS STATED ON MECH PLANS> |
| | PLEASE ADJUST AND CORRELATE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRLELATE ALL A/C |
| | SYSTEMS, OCP AND LOADS, AS THESE SHOWN |
| | ON ELECTRICAL PANEL SCHEDULE DO NOT |
| | MATCH WITH THOSE AS SHOWN ON MECH |
| | SHEETS. |
| | |
| | 24) NOTE:SAME, IF SHOWN THIS WAY OK, |
| | HOWEVER SIZE WILL BE REQUIRED TO BE |
| | REVISED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE VERIFY THE SIZE OF THE |
| | NEW METER CAN BEING SHOWN AS 225A?? THIS |
| | IS NOT KNOWN AS A COMMON SIZE. PLEASE |
| | ADJUST. |
| | 215.5 |
| | |
| | **** NEW NOTES **** |
| | |
| | 25) NOTE: PLEASE SEE NO HAND WRITTEN |
| | CHANGES CAN BE MADE TO PLANS WHICH ARE |
| | SIGNED , DATED AND SEALED BY THE |
| | ENGINEER. IF ANY CHANGES ARE MADE BY |
| | HAND, EACH AND EVERY ITEM SHALL CONTAIN |
| | INITIALS OF SAID DESIGNER AND DATE. |
| | FS 471.025, FAC 61G15-23.002 |
| | |
| | 26) NOTE: PLEASE SEE NOTICE GIVEN FOR |
| | FS553.80(2)9B). |
| | THIS IS ONLY A NOTICE. |
| | |
| | ** PLEASE KNOW,MANY OF THE ABOVE ITEMS |
| | ARE REDLINED ON ONE OF THE SETS OF |
| | PLANS, HOWEVER IS IN NO WAY ALL |
| | LOCATIONS AS NOTED ABOVE. |
| | |
| | ** PLEASE SUBMIT THE ABOVE FOR REVIEW |
| | AND IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |