Text |
| 2006-05-18 00:00:00 | DENIED |
| | |
| | |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.BASED ON ICC BUILDING VALUATION DATA |
| | THE PERMIT VALUE IS TOO LOW.REVISE |
| | PERMIT VALUE TO INCLUED ALL WORK AND PAY |
| | ADDITIONAL PERMIT FEES. |
| | |
| | 4.SUBMIT TWO COPIES OF ENERGY CALCS |
| | PER 2004 FBC. |
| | |
| | 5.PRODUCT APPROVALS REQUIRED FOR |
| | EXTERIOR DOORS, WINDOWS AND IMPACT |
| | PROTECTION. |
| | |
| | 6.ALL PRODUCT APPROVALS SUBMITTED WITH |
| | QUALITY ASSURANCE SHALL HAVE THE |
| | FOLLOWING STATE APPROVAL ATTACHED. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL |
| | SHEETS THAT LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. IF THE PRODUCT |
| | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT |
| | AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 7.THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMENDMENT TO FBC 106.3.3. |
| | |
| | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS |
| | FOR REVIEW PER 2004 FBC R-802.10.1 |
| | |
| | 9.A DESIGN PROFESSIONAL OR AN OWNER |
| | MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | SHOW HOW PLANS WILL COMPLY WITH THE |
| | SECTION(S) SELECTED.2004 FBC EXISTING |
| | BUILDING 301.5 |
| | |
| | 10.SUBMIT PLANS FOR NEW OFFICES. |
| | |
| | 11.SHOW EXISTING AND NEW SQUARE |
| | FOOTAGE CALCUALATIONS FOR ALL AREAS. |
| | |
| | 12.SHOW SIZE AND LOCATION OF ATTIC |
| | ACCESS COMPLYING WITH FBC 2004 R 807.1 |
| | |
| | 13.SQUARE FOOTAGE NOT SHOWN ON |
| | APPLICATION.APPLICATION DOES NOT |
| | REFLECT WORK THAT IS SHOWN ON PLANS. |
| | |
| | 14.BUILDING IS IN AN AREA OF |
| | QUESTIONABLE SOILS. SUBMIT A SOILS |
| | REPORT WITH FOOTING RECOMMENDATIONS. |
| | |
| | 15.SUBMIT AN ELEVATION CERTIFICATE |
| | SHOWING FINISH FLOOR HEIGHT.FINISH |
| | FLOOR HEIGHT IN THIS AREA IS 6" ABOVE |
| | THE BASE ELEVATION OF 7FT.SHOW FINISH |
| | FLOOR HEIGHT ON PLANS. |
| | |
| | 16.SHOW GUARDRAIL DETAILS COMPLYING |
| | WITH 2004 FBC R-312.1 AND R-312.2 |
| | |
| | 17.SUBMIT TWO ORIGONAL SIGNED AND |
| | SEALED SURVEYS. FS 472.025 |
| | |
| | 18.SHOW BUILDING ELEVATIONS ON PLANS. |
| | |
| | 19.SHOW CROSS SECTIONS FROM FOUNDATION |
| | UP THROUGH ROOF. |
| | |
| | 20.PS-1 CALLS FOR 5/8" ROOF SHEATHING |
| | AND OTHER AREAS ON PLAN SPEC FOR 3/4" |
| | SHEATHING. |
| | |
| | 21.INSUFFICIENT INFORMATION PROVIDED |
| | FOR A COMPLETE REVIEW. SEE WPB |
| | AMMENDMENTS TO THE FBC 106.3.5.1.1 FOR |
| | MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS.ADDITIONAL COMMENTS MAY |
| | ARISE AT THE NEXT PLAN REVIEW. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | OLD PAGES FOR REFERENCE. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ART LANGE |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | BUILDING PLANS EXAMINER |
| | 561-805-6672 |