| Plan Review Notes For Permit 06040623 |
| Permit Number |
06040623 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2007-10-01 08:33:11 | DENIED; | | | 1.SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 2. TYPE OF GAS, (LP OR NATURAL) | | | 3. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 4. GAS APPIANCE NOT LISTED ON PLANS. | | | 5. SEPARATE GAS PERMIT REQUIRED. ( NO PERMIT ON FILE ) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|